c/kWh
Energy rating (cooling)
1
Heating: 0
Annual electricity use
26,135 kWh
Estimated running cost
$8,363 / year
$697 / month Β· $83,632 over 10 years
Capacity
187.5 kW cooling
180.4 kW heating

1% more electricity than the median of 54 comparable 80 kW and above reverse cycle ducted packaged registrations (25,969 kWh a year) in the mixed zone. Uses less than 48% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Actron Air PKV2000T running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 17,310$5,539$55,392
Mixed zone 26,135$8,363$83,632
Hot zone 76,899$24,608$246,077

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 187.5 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P170AHR3SA-CRR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
APAC P170AHR3SA-CBR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
Daikin UAXYA170SY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Daikin UAXYA170NY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling24,120 kWh/yr1.5$7,718

Air conditioners similar to the Actron Air PKV2000T

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Temperzone OPA2000RKTMG-P186.1 kW heating183.6 kW cooling25,802 kWh/yr1$8,257
Temperzone FPA1700RKTMGQ-P182.1 kW heating182.9 kW cooling25,744 kWh/yr1$8,238
Carrier 50FC-180190 kW heating181 kW cooling65,242 kWh/yr1.5$20,877
AIRSTAGE URT-EC-WP-MS-172-SK208 kW heating195 kW cooling60,813 kWh/yr1.5$19,460
AIRSTAGE URT.EC.WP.MS 111 S.K208 kW heating195 kW cooling60,813 kWh/yr1.5$19,460
Carrier 50FC-180 R454b184 kW heating176 kW cooling66,529 kWh/yr1.5$21,289
APAC P170AHR3SA-164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
APAC P170AHR3SA-CRR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299

Compare PKV2000T with another model

Actron Air PKV2000T specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
187.50 kW
Cooling power input
61.75 kW
Rated heating capacity (7 Β°C)
180.45 kW
Heating power input
59.60 kW
EER, full load (tested)
2.99
COP, full load (tested)
2.93
Rated AEER
3.01
Rated ACOP
3.00
Standby power (PIA)
160.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Actron Air PKV2000T zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––39,767–
Coldresidential1.00.017,310–
Mixedcommercial––49,009–
Mixedresidential1.00.026,135–
Hotcommercial––105,755–
Hotresidential1.50.076,899–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

Australian GEMS registration details

Registration number
AAC6842
GEMS registration id
148527
Status
approved, available (self-reported)
Registration expires
30 September 2027
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
Simulation
MEPS
2020
Product class
Class 24

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: actronair.com.au. How the derived figures are calculated.