c/kWh
Energy rating (cooling)
1.5
Heating: 0
Annual electricity use
7,171 kWh
Estimated running cost
$2,295 / year
$191 / month Β· $22,947 over 10 years
Capacity
51.6 kW cooling
52.8 kW heating

15% less electricity than the median of 24 comparable 50 kW reverse cycle ducted packaged registrations (8,422 kWh a year) in the mixed zone. Uses less than 63% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 11% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Aggreko RPA-050D-R410A running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 4,725$1,512$15,120
Mixed zone 7,171$2,295$22,947
Hot zone 21,377$6,841$68,406

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 51.6 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P043AHR3SA-RRR47.1 kW heating45.9 kW cooling5,374 kWh/yr1.5$1,720
APAC P043AHR3SA-LTT47.1 kW heating45.9 kW cooling5,374 kWh/yr1.5$1,720
Caa VPA045R3AC49.4 kW heating46.1 kW cooling5,640 kWh/yr1.5$1,805
Caa HPA045R3AD50.4 kW heating46.5 kW cooling5,967 kWh/yr1.5$1,909
Actron Air PKY500T51.8 kW heating49.1 kW cooling6,700 kWh/yr1$2,144

Air conditioners similar to the Aggreko RPA-050D-R410A

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Coates RPA-C05052.8 kW heating51.6 kW cooling7,171 kWh/yr1.5$2,295
AIRSTAGE RAQ/K/EC/WP/12050.2 kW heating51.2 kW cooling13,522 kWh/yr2$4,327
AIRSTAGE RAQ/K/EC/WP/ECO/12050.2 kW heating51.2 kW cooling13,522 kWh/yr2$4,327
Temperzone OPA550RKTB52.6 kW heating52 kW cooling7,466 kWh/yr1$2,389
Gree GK-H15TC(1)/NhA-M(A)56.2 kW heating51 kW cooling14,933 kWh/yr2$4,779
Braemar RTHV500D3S56.2 kW heating51 kW cooling14,933 kWh/yr2$4,779
Temperzone OPA550RKTBG-P53.4 kW heating52.9 kW cooling7,577 kWh/yr1$2,425
Daikin UAYQ180CY1A56.1 kW heating53.1 kW cooling40,714 kWh/yr1$13,028

Compare RPA-050D-R410A with another model

Aggreko RPA-050D-R410A specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
51.60 kW
Cooling power input
17.27 kW
Rated heating capacity (7 Β°C)
52.76 kW
Heating power input
17.27 kW
EER, full load (tested)
2.96
COP, full load (tested)
2.95
Rated AEER
2.98
Rated ACOP
3.05
Standby power (PIA)
10.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Aggreko RPA-050D-R410A zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––11,014–
Coldresidential1.50.04,725–
Mixedcommercial––13,598–
Mixedresidential1.50.07,171–
Hotcommercial––29,471–
Hotresidential1.50.021,377–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

Australian GEMS registration details

Registration number
AAC7771
GEMS registration id
156654
Status
approved, available (self-reported)
Registration expires
11 September 2028
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 7

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. Manufacturer: coldmagic.com.cn. How the derived figures are calculated.