c/kWh
Energy rating (cooling)
1.5
Heating: 1
Annual electricity use
8,110 kWh
3,259 cooling + 4,851 heating
Estimated running cost
$2,595 / year
$216 / month Β· $25,952 over 10 years
Capacity
24.5 kW cooling
24.9 kW heating

2% more electricity than the median of 17 comparable 25 kW reverse cycle ducted packaged registrations (7,960 kWh a year) in the mixed zone. Uses less than 41% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 10% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

AIRSTAGE RAQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 14,262$4,564$45,638
Mixed zone 8,110$2,595$25,952
Hot zone 10,387$3,324$33,238

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 24.5 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Actron Air PRV22AT23 kW heating22 kW cooling5,387 kWh/yr2.5$1,724
Actron Air PRV25AT26 kW heating24.9 kW cooling6,315 kWh/yr2.5$2,021
APAC P020AHR3SA-18.9 kW heating22.4 kW cooling6,372 kWh/yr1.5$2,039
APAC P020AHR3SA-LRR18.9 kW heating22.4 kW cooling6,372 kWh/yr1.5$2,039
Temperzone OPA250RLTFPQ26.9 kW heating24.6 kW cooling7,030 kWh/yr2.5$2,250

Air conditioners similar to the AIRSTAGE RAQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Temperzone OPA250RLTFPQ26.9 kW heating24.6 kW cooling7,030 kWh/yr2.5$2,250
Actron Air PCG260U25.3 kW heating24.7 kW cooling7,960 kWh/yr1.5$2,547
Actron Air PRV25AT26 kW heating24.9 kW cooling6,315 kWh/yr2.5$2,021
APAC P024AVR3SA-LTS20.4 kW heating23.4 kW cooling6,987 kWh/yr1.5$2,236
APAC P024AHR3SA20.4 kW heating23.4 kW cooling6,987 kWh/yr1.5$2,236
Temperzone OPA242RKTB22 kW heating22.4 kW cooling7,114 kWh/yr1.5$2,276

Other AIRSTAGE models of similar capacity

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/K/WP/* 11024.8 kW heating24.4 kW cooling8,184 kWh/yr1.5$2,619
AIRSTAGE RAQ/K/WP/11024.8 kW heating24.4 kW cooling8,184 kWh/yr1.5$2,619

Compare RAQ/K/EC/WP/*110 with another model

AIRSTAGE RAQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
24.50 kW
Cooling power input
7.70 kW
Rated heating capacity (7 Β°C)
24.90 kW
Heating power input
7.60 kW
EER, full load (tested)
3.19
COP, full load (tested)
3.33
Rated AEER
3.15
Rated ACOP
3.25
Standby power (PIA)
20.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

AIRSTAGE RAQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,9594,125
Coldresidential1.51.02,15912,103
Mixedcommercial––6,1112,261
Mixedresidential1.51.03,2594,851
Hotcommercial––13,187506
Hotresidential1.51.09,589798
Part-load test points (4 values)
h__h2_full_cap_power_rated
7110 W
h__h3_have_full_cap_results
No
h__h2_full_cap_heat_cap_rated
21690 W
c__low_temp_have_full_cap_results
No

Other model numbers on registration AAC6601

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC6601
GEMS registration id
145920
Status
approved, available (self-reported)
Registration expires
6 April 2027
Registered for sale in
Australia, New Zealand
Family
RAQ/K/EC/WP/*110
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: fujitsugeneral.com.au. How the derived figures are calculated.