c/kWh
Energy rating (cooling)
2
Heating: 1
Annual electricity use
7,060 kWh
2,662 cooling + 4,398 heating
Estimated running cost
$2,259 / year
$188 / month Β· $22,592 over 10 years
Capacity
22.8 kW cooling
22.8 kW heating

11% less electricity than the median of 17 comparable 25 kW reverse cycle ducted packaged registrations (7,960 kWh a year) in the mixed zone. Uses less than 65% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 11% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

APAC P023AHR3TA-CI2061A running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 13,397$4,287$42,870
Mixed zone 7,060$2,259$22,592
Hot zone 8,260$2,643$26,432

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 22.8 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Actron Air PRV22AT23 kW heating22 kW cooling5,387 kWh/yr2.5$1,724
Actron Air PKV240T-T23.4 kW heating20.8 kW cooling5,980 kWh/yr2$1,914
APAC P020AVR3SA-LTR18.9 kW heating22.4 kW cooling6,372 kWh/yr1.5$2,039
APAC P020AHR3SA-RBB18.9 kW heating22.4 kW cooling6,372 kWh/yr1.5$2,039

Air conditioners similar to the APAC P023AHR3TA-CI2061A

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Actron Air PCG233V23.6 kW heating22.9 kW cooling6,986 kWh/yr1.5$2,236
Actron Air PCG233U23.6 kW heating22.9 kW cooling6,986 kWh/yr1.5$2,236
Temperzone OPA242RKTB22 kW heating22.4 kW cooling7,114 kWh/yr1.5$2,276
AIRSTAGE RAQ/IL/EC/WP/11024.3 kW heating23.8 kW cooling7,081 kWh/yr2$2,266
AIRSTAGE RAQ/K/WP/11024.8 kW heating24.4 kW cooling8,184 kWh/yr1.5$2,619
Temperzone OPA250RLTFPQ26.9 kW heating24.6 kW cooling7,030 kWh/yr2.5$2,250

Other APAC models of similar capacity

ModelStarsEst. cost / yrCompare
APAC P020AHR3SA18.9 kW heating22.4 kW cooling6,372 kWh/yr1.5$2,039
APAC P020AHR3SA-RRR18.9 kW heating22.4 kW cooling6,372 kWh/yr1.5$2,039

Compare P023AHR3TA-CI2061A with another model

APAC P023AHR3TA-CI2061A specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
22.82 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
22.84 kW
Heating power input
–
EER, full load (tested)
3.34
COP, full load (tested)
3.42
Rated AEER
3.33
Rated ACOP
3.49
Standby power (PIA)
29.8 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

APAC P023AHR3TA-CI2061A zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,9963,810
Coldresidential2.01.01,73411,663
Mixedcommercial––4,9491,937
Mixedresidential2.01.02,6624,398
Hotcommercial––10,316426
Hotresidential2.01.57,605655
Part-load test points (23 values)
c__t1_min_cap_power_rated
3310 W
h__h1_min_cap_power_rated
3010 W
h__h2_ext_cap_power_rated
5620 W
c__t1_half_cap_power_rated
3490 W
c__t1_have_min_cap_results
Yes
h__h1_half_cap_power_rated
3250 W
h__h1_have_min_cap_results
Yes
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_min_cap_heat_cap_rated
10620 W
h__h2_ext_cap_heat_cap_rated
15810 W
h__h1_half_cap_heat_cap_rated
11280 W
h__h2_is_capable_extended_load
Yes
c__low_temp_min_cap_power_rated
3210 W
c__t1_min_cap_cooling_cap_rated
11070 W
c__low_temp_half_cap_power_rated
3140 W
c__t1_half_cap_cooling_cap_rated
12030 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_min_cap_cooling_cap_rated
12820 W
c__low_temp_half_cap_cooling_cap_rated
14100 W

Other model numbers on registration AAC10333

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC10333
GEMS registration id
–
Status
approved
Registration expires
26 July 2031
Registered for sale in
Australia, New Zealand
Family
P023AHR3TA-
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
6

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. How the derived figures are calculated.