c/kWh
Energy rating (cooling)
3.5
Heating: 0
Annual electricity use
4,915 kWh
Estimated running cost
$1,573 / year
$131 / month Β· $15,728 over 10 years
Capacity
61.5 kW cooling
61.5 kW heating

70% less electricity than the median of 25 comparable 65 kW reverse cycle multi-split / vrf registrations (16,281 kWh a year) in the mixed zone. Uses less than 96% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 17% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Carrier 38VT022188QTSG running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 3,109$995$9,949
Mixed zone 4,915$1,573$15,728
Hot zone 14,543$4,654$46,538

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 61.5 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Carrier 38VT020188QTSG56 kW heating56 kW cooling4,381 kWh/yr3.5$1,402

Air conditioners similar to the Carrier 38VT022188QTSG

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin REYQ22BYM969 kW heating61.5 kW cooling21,640 kWh/yr2$6,925
Hitachi RAS-22FSXNS69 kW heating61.5 kW cooling8,410 kWh/yr1$2,691
Daikin RXYQ22BYM69 kW heating61.5 kW cooling21,490 kWh/yr2$6,877
Mdv MV8-615WV2RN1E(MA)61.5 kW heating61.5 kW cooling19,134 kWh/yr2$6,123
Midea MV8-615WV2RN1E(MA)61.5 kW heating61.5 kW cooling19,134 kWh/yr2$6,123
Samsung Electronics AM220DXVGGH/SA69.3 kW heating61.6 kW cooling15,699 kWh/yr2.5$5,024
Samsung Electronics AM220DXVGGR/SA69.3 kW heating61.6 kW cooling15,699 kWh/yr2.5$5,024
LG ARUM221LTE669.3 kW heating61.6 kW cooling13,842 kWh/yr3$4,429

Compare 38VT022188QTSG with another model

Carrier 38VT022188QTSG specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
61.50 kW
Cooling power input
15.44 kW
Rated heating capacity (7 Β°C)
61.50 kW
Heating power input
15.13 kW
EER, full load (tested)
3.82
COP, full load (tested)
3.94
Rated AEER
3.97
Rated ACOP
4.05
Standby power (PIA)
19.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
China, Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Carrier 38VT022188QTSG zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,873–
Coldresidential3.50.03,109–
Mixedcommercial––8,694–
Mixedresidential3.50.04,915–
Hotcommercial––19,508–
Hotresidential4.00.014,543–
Part-load test points (5 values)
c__t1_half_cap_power_rated
5510 W
c__t1_have_min_cap_results
No
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
30750 W
c__low_temp_have_half_cap_results
No

Australian GEMS registration details

Registration number
AAC9626
GEMS registration id
174122
Status
approved, available (self-reported)
Registration expires
2 December 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.