c/kWh
Energy rating (cooling)
2.5
Heating: 2
Annual electricity use
9,053 kWh
3,175 cooling + 5,878 heating
Estimated running cost
$2,897 / year
$241 / month Β· $28,970 over 10 years
Capacity
33.5 kW cooling
37.5 kW heating

7% more electricity than the median of 20 comparable 35 kW reverse cycle multi-split / vrf registrations (8,491 kWh a year) in the mixed zone. Uses less than 35% of them.

Across all 3,681 air conditioner registrations sold in Australia, it uses less than 9% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Hitachi RAS-120RNCCLW running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 18,747$5,999$59,990
Mixed zone 9,053$2,897$28,970
Hot zone 9,390$3,005$30,048

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 33.5 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Panasonic U-12MF3R737.5 kW heating33.5 kW cooling2,717 kWh/yr3$869
Toshiba MMY-MUP12S1HT8P-A37.5 kW heating33.5 kW cooling3,022 kWh/yr2.5$967
Mitsubishi Electric PUHY-M300YXM-A33.5 kW heating33.5 kW cooling4,042 kWh/yr1.5$1,293
Mitsubishi Electric PUHY-M300YXM series33.5 kW heating33.5 kW cooling4,042 kWh/yr1.5$1,293
Hitachi RAS-120RNCBLW37.5 kW heating33.5 kW cooling7,724 kWh/yr2.5$2,472

Air conditioners similar to the Hitachi RAS-120RNCCLW

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Mitsubishi Electric PUHY-M300YXM-A-BS33.5 kW heating33.5 kW cooling4,042 kWh/yr1.5$1,293
Panasonic U-12MF3R737.5 kW heating33.5 kW cooling2,717 kWh/yr3$869
Mitsubishi Electric PUHY-M300YXM series33.5 kW heating33.5 kW cooling4,042 kWh/yr1.5$1,293
Mitsubishi Heavy Industries FDC335KXZE333.5 kW heating33.5 kW cooling8,260 kWh/yr3$2,643
Toshiba MMY-MUP12S1HT8P-A37.5 kW heating33.5 kW cooling3,022 kWh/yr2.5$967
Toshiba MMY-MUP1201FT8P-A33.5 kW heating33.5 kW cooling7,779 kWh/yr3.5$2,489
Mitsubishi Heavy Industries FDC335KXZE3(A)33.5 kW heating33.5 kW cooling8,260 kWh/yr3$2,643
Daikin REYA12AYM37.5 kW heating33.5 kW cooling7,745 kWh/yr2.5$2,478

Compare RAS-120RNCCLW with another model

Hitachi RAS-120RNCCLW specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
33.50 kW
Cooling power input
8.38 kW
Rated heating capacity (7 Β°C)
37.50 kW
Heating power input
8.80 kW
EER, full load (tested)
3.85
COP, full load (tested)
4.03
Rated AEER
3.80
Rated ACOP
4.06
Standby power (PIA)
130.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Hitachi RAS-120RNCCLW zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,1645,128
Coldresidential2.01.02,11016,637
Mixedcommercial––5,1632,655
Mixedresidential2.52.03,1755,878
Hotcommercial––11,091660
Hotresidential3.53.08,434956
Part-load test points (16 values)
h__h2_ext_cap_power_rated
9240 W
c__t1_half_cap_power_rated
3050 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
3460 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
24580 W
h__h1_half_cap_heat_cap_rated
18750 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
16750 W
c__low_temp_have_half_cap_results
No

Australian GEMS registration details

Registration number
AAC7323
GEMS registration id
151035
Status
approved, available (self-reported)
Registration expires
1 March 2028
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 20

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: temperzone.com. How the derived figures are calculated.