Hitachi RAS-160RNCCLW is a 45 kW reverse cycle multi-split / vrf air conditioner registered under Australiaβs Energy Rating (GEMS) scheme (registration AAC7330).
- Energy rating (cooling)
- 2.5
- Heating: 2.5
- Annual electricity use
- 11,174 kWh
- 4,270 cooling + 6,904 heating
- Estimated running cost
- $3,576 / year
- $298 / month Β· $35,757 over 10 years
- Capacity
- 45 kW cooling
- 50 kW heating
19% less electricity than the median of 42 comparable 50 kW reverse cycle multi-split / vrf registrations (13,803 kWh a year) in the mixed zone. Uses less than 74% of them.
Across all 3,680 air conditioner registrations sold in Australia, it uses less than 7% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ 32c/kWh in AUD; change the price above to your tariff.
Hitachi RAS-160RNCCLW running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 22,015 | $7,045 | $70,448 |
| Mixed zone | 11,174 | $3,576 | $35,757 |
| Hot zone | 12,758 | $4,083 | $40,826 |
At 32c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Air conditioners that use less electricity
Same configuration and type, cooling capacity within 12% of 45 kW, at least 3% lower annual kWh in the mixed zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr | 2.5 | $1,254 | |
| Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr | 2.5 | $1,300 | |
| Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr | 2.5 | $1,422 | |
| Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling5,003 kWh/yr | 1.5 | $1,601 | |
| Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr | 1.5 | $1,601 |
Air conditioners similar to the Hitachi RAS-160RNCCLW
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Mitsubishi Heavy Industries FDC450KXZE250 kW heating45 kW cooling11,292 kWh/yr | 2.5 | $3,613 | |
| Daikin REYA16AYM50 kW heating45 kW cooling11,471 kWh/yr | 3 | $3,671 | |
| Mitsubishi Electric PUHY-M400YXM-A45 kW heating45 kW cooling5,655 kWh/yr | 1.5 | $1,810 | |
| Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr | 2.5 | $1,422 | |
| Mitsubishi Heavy Industries FDC450KXZRE245 kW heating45 kW cooling11,109 kWh/yr | 2 | $3,555 | |
| Daikin REYQ16TAY150 kW heating45 kW cooling14,331 kWh/yr | 2 | $4,586 | |
| Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr | 2.5 | $1,300 | |
| Mitsubishi Electric PUHY-M400YXM-A-BS45 kW heating45 kW cooling5,655 kWh/yr | 1.5 | $1,810 |
Compare RAS-160RNCCLW with another model
Hitachi RAS-160RNCCLW specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 45.00 kW
- Cooling power input
- 12.18 kW
- Rated heating capacity (7 Β°C)
- 50.00 kW
- Heating power input
- 13.33 kW
- EER, full load (tested)
- 3.54
- COP, full load (tested)
- 3.89
- Rated AEER
- 3.55
- Rated ACOP
- 3.61
- Standby power (PIA)
- 149.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- China
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Hitachi RAS-160RNCCLW zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 5,561 | 6,166 |
| Coldresidential | residential | 2.5 | 1.5 | 2,794 | 19,221 |
| Mixedcommercial | commercial | β | β | 6,956 | 3,070 |
| Mixedresidential | residential | 2.5 | 2.5 | 4,270 | 6,904 |
| Hotcommercial | commercial | β | β | 15,171 | 824 |
| Hotresidential | residential | 3.0 | 3.5 | 11,551 | 1,207 |
Part-load test points (16 values)
- h__h2_ext_cap_power_rated
- 14060 W
- c__t1_half_cap_power_rated
- 4080 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 4550 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 38040 W
- h__h1_half_cap_heat_cap_rated
- 25000 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 22500 W
- c__low_temp_have_half_cap_results
- No
Australian GEMS registration details
- Registration number
- AAC7330
- GEMS registration id
- 151038
- Status
- approved, available (self-reported)
- Registration expires
- 1 March 2028
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 21