Australia Β· costs in AUD

Reverse cycle multi-split / vrf air conditioner
Hitachi RAS-200RNCCLW Air Conditioner
Hitachi RAS-200RNCCLW is a 56 kW reverse cycle multi-split / vrf air conditioner registered under Australiaβs Energy Rating (GEMS) scheme (registration AAC7326).
- Energy rating (cooling)
- 2.5
- Heating: 2
- Annual electricity use
- 15,079 kWh
- 5,257 cooling + 9,822 heating
- Estimated running cost
- $4,825 / year
- $402 / month Β· $48,253 over 10 years
- Capacity
- 56 kW cooling
- 63 kW heating
9% more electricity than the median of 42 comparable 50 kW reverse cycle multi-split / vrf registrations (13,803 kWh a year) in the mixed zone. Uses less than 36% of them.
Across all 3,681 air conditioner registrations sold in Australia, it uses less than 4% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ 32c/kWh in AUD; change the price above to your tariff.
Hitachi RAS-200RNCCLW running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 31,030 | $9,930 | $99,296 |
| Mixed zone | 15,079 | $4,825 | $48,253 |
| Hot zone | 15,436 | $4,940 | $49,395 |
At 32c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Air conditioners that use less electricity
Same configuration and type, cooling capacity within 12% of 56 kW, at least 3% lower annual kWh in the mixed zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling5,421 kWh/yr | 2.5 | $1,735 | |
| Toshiba MMY-MUP2201FT8P-A61.5 kW heating61.5 kW cooling5,429 kWh/yr | 3 | $1,737 | |
| Mitsubishi Electric PUHY-M450YXM-A50 kW heating50 kW cooling6,542 kWh/yr | 1.5 | $2,093 | |
| Mitsubishi Electric PUHY-M450YXM series50 kW heating50 kW cooling6,542 kWh/yr | 1.5 | $2,093 | |
| Hitachi RAS-180RNCCLW56 kW heating50.4 kW cooling11,937 kWh/yr | 2.5 | $3,820 |
Air conditioners similar to the Hitachi RAS-200RNCCLW
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Mitsubishi Heavy Industries FDC560KXZE263 kW heating56 kW cooling16,171 kWh/yr | 2.5 | $5,175 | |
| Mitsubishi Electric PUHY-M500YXM series56 kW heating56 kW cooling8,090 kWh/yr | 1 | $2,589 | |
| Mitsubishi Electric PUHY-M500YXM-A56 kW heating56 kW cooling8,090 kWh/yr | 1 | $2,589 | |
| Daikin REYA20AYM63 kW heating56 kW cooling13,423 kWh/yr | 3 | $4,295 | |
| Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling5,421 kWh/yr | 2.5 | $1,735 | |
| Toshiba MMY-MUP2001FT8P-A56 kW heating56 kW cooling16,337 kWh/yr | 3 | $5,228 | |
| Daikin REYQ20TAY163 kW heating56 kW cooling19,870 kWh/yr | 2 | $6,358 |
Other Hitachi models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Hitachi RAS-200RNCBLW63 kW heating56 kW cooling13,993 kWh/yr | 2 | $4,478 |
Compare RAS-200RNCCLW with another model
Hitachi RAS-200RNCCLW specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 56.00 kW
- Cooling power input
- 13.44 kW
- Rated heating capacity (7 Β°C)
- 63.00 kW
- Heating power input
- 14.36 kW
- EER, full load (tested)
- 3.93
- COP, full load (tested)
- 4.55
- Rated AEER
- 3.93
- Rated ACOP
- 4.15
- Standby power (PIA)
- 240.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- China
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Hitachi RAS-200RNCCLW zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 6,857 | 8,579 |
| Coldresidential | residential | 2.0 | 1.5 | 3,519 | 27,511 |
| Mixedcommercial | commercial | β | β | 8,472 | 4,209 |
| Mixedresidential | residential | 2.5 | 2.0 | 5,257 | 9,822 |
| Hotcommercial | commercial | β | β | 18,065 | 1,158 |
| Hotresidential | residential | 3.5 | 3.0 | 13,767 | 1,669 |
Part-load test points (16 values)
- h__h2_ext_cap_power_rated
- 15230 W
- c__t1_half_cap_power_rated
- 4970 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 5870 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 41980 W
- h__h1_half_cap_heat_cap_rated
- 31500 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 28000 W
- c__low_temp_have_half_cap_results
- No
Australian GEMS registration details
- Registration number
- AAC7326
- GEMS registration id
- 151041
- Status
- approved, available (self-reported)
- Registration expires
- 1 March 2028
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 21
Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: temperzone.com. How the derived figures are calculated.