c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
14,803 kWh
3,207 cooling + 11,596 heating
Estimated running cost
$4,737 / year
$395 / month Β· $47,370 over 10 years
Capacity
33.5 kW cooling
37.5 kW heating

74% more electricity than the median of 20 comparable 35 kW reverse cycle multi-split / vrf registrations (8,491 kWh a year) in the mixed zone. Uses less than 10% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 5% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-P300YNW-A1-BS running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 32,336$10,348$103,475
Mixed zone 14,803$4,737$47,370
Hot zone 10,264$3,284$32,845

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 33.5 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Panasonic U-12MF3R737.5 kW heating33.5 kW cooling2,717 kWh/yr3$869
Toshiba MMY-MUP12S1HT8P-A37.5 kW heating33.5 kW cooling3,022 kWh/yr2.5$967
Mitsubishi Electric PUHY-M300YXM-A-BS33.5 kW heating33.5 kW cooling4,042 kWh/yr1.5$1,293
Mitsubishi Electric PUHY-M300YXM series33.5 kW heating33.5 kW cooling4,042 kWh/yr1.5$1,293
Hitachi RAS-120RNCBLW37.5 kW heating33.5 kW cooling7,724 kWh/yr2.5$2,472

Air conditioners similar to the Mitsubishi Electric PUHY-P300YNW-A1-BS

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Hitachi RAS-120HNCELW37.5 kW heating33.5 kW cooling7,963 kWh/yr2.5$2,548
Mitsubishi Heavy Industries FDC335KXZE333.5 kW heating33.5 kW cooling8,260 kWh/yr3$2,643
Mitsubishi Heavy Industries FDC335KXZE3A33.5 kW heating33.5 kW cooling8,260 kWh/yr3$2,643
Panasonic U-12MF3R737.5 kW heating33.5 kW cooling2,717 kWh/yr3$869
Toshiba MMY-MUP1201FT8P-A33.5 kW heating33.5 kW cooling7,779 kWh/yr3.5$2,489
Toshiba MMY-MUP12S1HT8P-A37.5 kW heating33.5 kW cooling3,022 kWh/yr2.5$967
Hitachi RAS-120RNCBLW37.5 kW heating33.5 kW cooling7,724 kWh/yr2.5$2,472
Daikin REYA12AYM37.5 kW heating33.5 kW cooling7,745 kWh/yr2.5$2,478

Compare PUHY-P300YNW-A1-BS with another model

Mitsubishi Electric PUHY-P300YNW-A1-BS specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
33.50 kW
Cooling power input
9.09 kW
Rated heating capacity (7 Β°C)
37.50 kW
Heating power input
9.67 kW
EER, full load (tested)
3.72
COP, full load (tested)
4.20
Rated AEER
3.60
Rated ACOP
3.79
Standby power (PIA)
65.1 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-P300YNW-A1-BS zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,1428,265
Coldresidential2.50.02,09230,244
Mixedcommercial––5,3234,106
Mixedresidential2.50.03,20711,596
Hotcommercial––11,874741
Hotresidential3.01.59,0601,204
Part-load test points (18 values)
h__h2_ext_cap_power_rated
8300 W
c__t1_half_cap_power_rated
3620 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
4650 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
15800 W
h__h1_half_cap_heat_cap_rated
18700 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
2980 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
16750 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
16750 W

Other model numbers on registration AAC9285

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9285
GEMS registration id
171899
Status
approved, available (self-reported)
Registration expires
24 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-P300YNW-A1 Series
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 20

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.