c/kWh
Energy rating (cooling)
2
Heating: 0
Annual electricity use
24,364 kWh
5,088 cooling + 19,276 heating
Estimated running cost
$7,796 / year
$650 / month Β· $77,965 over 10 years
Capacity
50 kW cooling
56 kW heating

79% more electricity than the median of 41 comparable 50 kW reverse cycle registrations (13,613 kWh a year) in the mixed zone. Uses less than 12% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-P450YNW-A1 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 52,301$16,736$167,363
Mixed zone 24,364$7,796$77,965
Hot zone 16,517$5,285$52,854

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 50 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr2.5$1,300
Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr2.5$1,422
Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling5,421 kWh/yr2.5$1,735
Mitsubishi Electric PUHY-M400YXM-A-BS45 kW heating45 kW cooling5,655 kWh/yr1.5$1,810
Mitsubishi Electric PUHY-M400YXM-A45 kW heating45 kW cooling5,655 kWh/yr1.5$1,810

Air conditioners similar to the Mitsubishi Electric PUHY-P450YNW-A1

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Mitsubishi Heavy Industries FDC500KXZRE250 kW heating50 kW cooling14,484 kWh/yr2$4,635
Daikin REYA18AYM56 kW heating50 kW cooling13,077 kWh/yr2.5$4,185
Daikin REYQ18TAY156 kW heating50 kW cooling17,011 kWh/yr2$5,444
Toshiba MMY-MUP1801FT8P-A50.4 kW heating50.4 kW cooling14,382 kWh/yr3$4,602
Toshiba MMY-MUP18S1HT8P-A54 kW heating50.4 kW cooling5,465 kWh/yr2$1,749
Hitachi RAS-180RNCCLW56 kW heating50.4 kW cooling11,937 kWh/yr2.5$3,820
Hitachi RAS-180RNCBLW56 kW heating50.4 kW cooling12,411 kWh/yr2$3,972

Other Mitsubishi Electric models of similar capacity

ModelStarsEst. cost / yrCompare
Mitsubishi Electric PUHY-M450YXM-A-BS50 kW heating50 kW cooling6,542 kWh/yr1.5$2,093

Compare PUHY-P450YNW-A1 with another model

Mitsubishi Electric PUHY-P450YNW-A1 specifications

Type
Reverse cycle
Configuration
–
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
50.00 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
56.00 kW
Heating power input
–
EER, full load (tested)
3.40
COP, full load (tested)
3.96
Rated AEER
3.34
Rated ACOP
3.65
Standby power (PIA)
81.4 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-P450YNW-A1 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,58612,410
Coldresidential2.50.03,30248,999
Mixedcommercial––8,5036,479
Mixedresidential2.00.05,08819,276
Hotcommercial––19,0791,149
Hotresidential2.51.014,5481,969
Part-load test points (18 values)
h__h2_ext_cap_power_rated
10600 W
c__t1_half_cap_power_rated
5880 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
6800 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
21000 W
h__h1_half_cap_heat_cap_rated
28000 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
4820 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
25000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
25000 W

Other model numbers on registration AAC9239

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9239
GEMS registration id
–
Status
approved
Registration expires
19 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-P450YNW-A1
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.