c/kWh
Energy rating (cooling)
2
Heating: 1
Annual electricity use
28,734 kWh
10,678 cooling + 18,056 heating
Estimated running cost
$9,195 / year
$766 / month Β· $91,949 over 10 years
Capacity
91 kW cooling
95.8 kW heating

11% more electricity than the median of 54 comparable 80 kW and above reverse cycle ducted packaged registrations (25,969 kWh a year) in the mixed zone. Uses less than 41% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Temperzone FPA 970RLTB2FPQD running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 52,473$16,791$167,914
Mixed zone 28,734$9,195$91,949
Hot zone 34,532$11,050$110,502

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 91 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Temperzone OPA855RKTBG-P77.6 kW heating81.4 kW cooling10,741 kWh/yr1.5$3,437
APAC P085AHR3SA-RTR80.8 kW heating84.1 kW cooling10,747 kWh/yr1.5$3,439
APAC P085AHR3SA-RTT80.8 kW heating84.1 kW cooling10,747 kWh/yr1.5$3,439
Temperzone OPA970RLTB1FPQ88.2 kW heating88.9 kW cooling12,461 kWh/yr1.5$3,988
Actron Air PRV85AT86 kW heating85 kW cooling21,630 kWh/yr2.5$6,922

Air conditioners similar to the Temperzone FPA 970RLTB2FPQD

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/K/EC/WP/*23692.6 kW heating90.4 kW cooling30,025 kWh/yr1.5$9,608
AIRSTAGE RAQ/K/EC/WP/23692.6 kW heating90.4 kW cooling30,025 kWh/yr1.5$9,608
APAC P095AHR3SA-92.2 kW heating94.1 kW cooling13,101 kWh/yr1$4,192
APAC P095AHR3SA-RTT92.2 kW heating94.1 kW cooling13,101 kWh/yr1$4,192
Daikin UAYN940AFY1A94 kW heating94.9 kW cooling32,488 kWh/yr1$10,396
Actron Air PRV96AT97 kW heating96 kW cooling25,238 kWh/yr2.5$8,076

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA960RKTBG-P88.9 kW heating92 kW cooling13,013 kWh/yr1$4,164
Temperzone OPA970RLTB1FPQ88.2 kW heating88.9 kW cooling12,461 kWh/yr1.5$3,988

Compare FPA 970RLTB2FPQD with another model

Temperzone FPA 970RLTB2FPQD specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
91.00 kW
Cooling power input
29.89 kW
Rated heating capacity (7 Β°C)
95.83 kW
Heating power input
28.68 kW
EER, full load (tested)
2.99
COP, full load (tested)
3.34
Rated AEER
3.04
Rated ACOP
3.33
Standby power (PIA)
23.0 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone FPA 970RLTB2FPQD zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––14,64115,893
Coldresidential2.01.06,89545,578
Mixedcommercial––18,9028,893
Mixedresidential2.01.010,67818,056
Hotcommercial––42,2621,885
Hotresidential2.01.031,6622,870
Part-load test points (25 values)
c__t1_min_cap_power_rated
9979 W
h__h1_min_cap_power_rated
8784 W
h__h2_ext_cap_power_rated
32102 W
c__t1_half_cap_power_rated
13619 W
c__t1_have_min_cap_results
Yes
h__h1_half_cap_power_rated
14801 W
h__h1_have_min_cap_results
Yes
h__h2_full_cap_power_rated
27091 W
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
Yes
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_min_cap_heat_cap_rated
22180 W
h__h2_ext_cap_heat_cap_rated
84908 W
h__h1_half_cap_heat_cap_rated
50050 W
h__h2_full_cap_heat_cap_rated
75789 W
h__h2_is_capable_extended_load
Yes
c__low_temp_min_cap_power_rated
8157 W
c__t1_min_cap_cooling_cap_rated
28060 W
c__low_temp_half_cap_power_rated
11701 W
c__t1_half_cap_cooling_cap_rated
45380 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_min_cap_cooling_cap_rated
28860 W
c__low_temp_half_cap_cooling_cap_rated
47270 W

Other model numbers on registration AAC7080

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC7080
GEMS registration id
141172
Status
approved, available (self-reported)
Registration expires
9 October 2027
Registered for sale in
Australia, Fiji, New Zealand
Family
OPA 970RLTB2FPQD
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.