c/kWh
Energy rating (cooling)
3
Heating: 2
Annual electricity use
16,073 kWh
5,965 cooling + 10,108 heating
Estimated running cost
$5,143 / year
$429 / month Β· $51,434 over 10 years
Capacity
65.1 kW cooling
64.5 kW heating

17% less electricity than the median of 16 comparable 65 kW reverse cycle ducted packaged registrations (19,275 kWh a year) in the mixed zone. Uses less than 69% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 4% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Temperzone OPA 680RLTB2FPDQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 29,720$9,510$95,104
Mixed zone 16,073$5,143$51,434
Hot zone 19,023$6,087$60,874

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 65.1 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P065AHR3SA-LTT62.9 kW heating63.5 kW cooling7,546 kWh/yr1.5$2,415
APAC P065AHR3SA-RTR62.9 kW heating63.5 kW cooling7,546 kWh/yr1.5$2,415
Temperzone OPA705RKTBG-P67.5 kW heating67.9 kW cooling8,618 kWh/yr1.5$2,758
Temperzone OPA705RKTB66.4 kW heating66 kW cooling8,618 kWh/yr1.5$2,758
Actron Air PKY620T62.5 kW heating60.8 kW cooling8,966 kWh/yr1$2,869

Air conditioners similar to the Temperzone OPA 680RLTB2FPDQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAYN640AFY1A64.9 kW heating66.2 kW cooling21,846 kWh/yr1.5$6,991
Daikin UAYQ210CY1A64 kW heating63.7 kW cooling20,787 kWh/yr1.5$6,652
APAC P065AHR3SA-LTT62.9 kW heating63.5 kW cooling7,546 kWh/yr1.5$2,415
APAC P065AHR3SA-RTR62.9 kW heating63.5 kW cooling7,546 kWh/yr1.5$2,415
AIRSTAGE RAQ/K/WP/* 23071.6 kW heating68.8 kW cooling24,417 kWh/yr1$7,813
AIRSTAGE RAQ/K/WP/ECO/23071.6 kW heating68.8 kW cooling24,417 kWh/yr1$7,813

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA 680RLTB1FPQ63.5 kW heating65 kW cooling16,746 kWh/yr2$5,359
Temperzone OPA705RKTB66.4 kW heating66 kW cooling8,618 kWh/yr1.5$2,758

Compare OPA 680RLTB2FPDQ with another model

Temperzone OPA 680RLTB2FPDQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
65.09 kW
Cooling power input
17.09 kW
Rated heating capacity (7 Β°C)
64.50 kW
Heating power input
16.51 kW
EER, full load (tested)
3.81
COP, full load (tested)
3.91
Rated AEER
3.78
Rated ACOP
3.88
Standby power (PIA)
39.0 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA 680RLTB2FPDQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––7,7668,547
Coldresidential3.01.53,85625,864
Mixedcommercial––10,1614,585
Mixedresidential3.02.05,96510,108
Hotcommercial––22,897994
Hotresidential3.02.017,4611,562
Part-load test points (18 values)
h__h2_ext_cap_power_rated
20670 W
c__t1_half_cap_power_rated
7960 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
7670 W
h__h1_have_min_cap_results
No
h__h2_half_cap_power_rated
8580 W
h__h2_have_half_cap_results
Yes
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
59827 W
h__h1_half_cap_heat_cap_rated
30730 W
h__h2_half_cap_heat_cap_rated
26890 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
6380 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
33690 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
33850 W

Australian GEMS registration details

Registration number
AAC8642
GEMS registration id
167485
Status
approved, available (self-reported)
Registration expires
11 March 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.