c/kWh
Energy rating (cooling)
2
Heating: 0
Annual electricity use
14,601 kWh
Estimated running cost
$4,672 / year
$389 / month Β· $46,723 over 10 years
Capacity
127.6 kW cooling
115.1 kW heating

44% less electricity than the median of 54 comparable 80 kW and above reverse cycle ducted packaged registrations (25,969 kWh a year) in the mixed zone. Uses less than 85% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 5% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Temperzone OPA1400RKTMDF-P running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 9,419$3,014$30,141
Mixed zone 14,601$4,672$46,723
Hot zone 43,444$13,902$139,021

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners similar to the Temperzone OPA1400RKTMDF-P

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Caa HPC125R3AD138.3 kW heating127.5 kW cooling17,106 kWh/yr1.5$5,474
AIRSTAGE URT-EC-WP-MS-111-SK136 kW heating127 kW cooling40,900 kWh/yr1.5$13,088
AIRSTAGE URT/EC/WP/MS/111/SK136 kW heating127 kW cooling40,900 kWh/yr1.5$13,088
Daikin UAXYA130NY1130 kW heating130 kW cooling18,763 kWh/yr1$6,004
Daikin UAXYA130RY1130 kW heating130 kW cooling18,763 kWh/yr1$6,004
Actron Air PKV1400T134 kW heating135 kW cooling19,152 kWh/yr1$6,129

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA1370RKTMG-P125.5 kW heating131.6 kW cooling17,279 kWh/yr1.5$5,529
Temperzone OPA1370RLTMFQ-P130.9 kW heating136.7 kW cooling18,423 kWh/yr1.5$5,895

Compare OPA1400RKTMDF-P with another model

Temperzone OPA1400RKTMDF-P specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
127.56 kW
Cooling power input
40.44 kW
Rated heating capacity (7 Β°C)
115.08 kW
Heating power input
34.60 kW
EER, full load (tested)
3.15
COP, full load (tested)
3.33
Rated AEER
3.14
Rated ACOP
3.31
Standby power (PIA)
53.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA1400RKTMDF-P zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––22,348–
Coldresidential2.00.09,419–
Mixedcommercial––27,453–
Mixedresidential2.00.014,601–
Hotcommercial––60,029–
Hotresidential2.00.043,444–
Part-load test points (7 values)
c__t1_half_cap_power_rated
17560 W
c__t1_have_min_cap_results
No
c__low_temp_half_cap_power_rated
15720 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
69760 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
67600 W

Australian GEMS registration details

Registration number
AAC7074
GEMS registration id
150356
Status
approved, available (self-reported)
Registration expires
5 October 2027
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.