c/kWh
Energy rating (cooling)
2
Heating: 1.5
Annual electricity use
49,570 kWh
18,984 cooling + 30,586 heating
Estimated running cost
$15,862 / year
$1,322 / month Β· $158,624 over 10 years
Capacity
177.9 kW cooling
184.1 kW heating

91% more electricity than the median of 54 comparable 80 kW and above reverse cycle ducted packaged registrations (25,969 kWh a year) in the mixed zone. Uses less than 17% of them.

Across all 3,681 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Temperzone OPA1710RLTM4FDPQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 92,691$29,661$296,611
Mixed zone 49,570$15,862$158,624
Hot zone 60,394$19,326$193,261

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 177.9 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P150AHR3SA-CBR146.6 kW heating156.7 kW cooling19,505 kWh/yr1.5$6,242
APAC P150AHR3SA-146.6 kW heating156.7 kW cooling19,505 kWh/yr1.5$6,242
Daikin UAXYA170NY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Daikin UAXYA170RY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling24,120 kWh/yr1.5$7,718

Air conditioners similar to the Temperzone OPA1710RLTM4FDPQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Carrier 50FC-180 R454b184 kW heating176 kW cooling66,529 kWh/yr1.5$21,289
Carrier 50FC-180190 kW heating181 kW cooling65,242 kWh/yr1.5$20,877
APAC P170AHR3SA-CTR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
APAC P170AHR3SA-CBR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
Daikin UAXYA170RY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Daikin UAXYA170NY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling24,120 kWh/yr1.5$7,718
Temperzone FPA1700RKTMGQ-P182.1 kW heating182.9 kW cooling25,744 kWh/yr1$8,238

Compare OPA1710RLTM4FDPQ with another model

Temperzone OPA1710RLTM4FDPQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
177.92 kW
Cooling power input
58.06 kW
Rated heating capacity (7 Β°C)
184.06 kW
Heating power input
56.72 kW
EER, full load (tested)
3.06
COP, full load (tested)
3.25
Rated AEER
3.06
Rated ACOP
3.24
Standby power (PIA)
46.0 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
–
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA1710RLTM4FDPQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––24,09326,102
Coldresidential2.51.012,11480,577
Mixedcommercial––31,85813,783
Mixedresidential2.01.518,98430,586
Hotcommercial––72,5882,840
Hotresidential2.52.055,8964,498
Part-load test points (18 values)
h__h2_ext_cap_power_rated
67779 W
c__t1_half_cap_power_rated
26120 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
24640 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
165732 W
h__h1_half_cap_heat_cap_rated
94513 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
21600 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
87800 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
99320 W

Australian GEMS registration details

Registration number
AAC8002
GEMS registration id
158739
Status
approved, available (self-reported)
Registration expires
14 January 2029
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.