c/kWh
Energy rating (cooling)
1
Heating: 0
Annual electricity use
12,525 kWh
Estimated running cost
$4,008 / year
$334 / month Β· $40,080 over 10 years
Capacity
88.7 kW cooling
90.4 kW heating

39% less electricity than the median of 14 comparable 80 kW and above reverse cycle ducted split system registrations (20,602 kWh a year) in the mixed zone. Uses less than 71% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 6% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Temperzone OSA950RKTBGV running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 8,257$2,642$26,422
Mixed zone 12,525$4,008$40,080
Hot zone 37,300$11,936$119,360

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 88.7 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Temperzone OSA840RKTBGV/ISD840KBXH-P78.3 kW heating81.3 kW cooling10,568 kWh/yr1.5$3,382
APAC S085OVR3SA/S085IHR3SA-TR80.8 kW heating84.1 kW cooling10,747 kWh/yr1.5$3,439
APAC S085OVR3SA- / S085IHR3SA--80.8 kW heating84.1 kW cooling10,747 kWh/yr1.5$3,439

Air conditioners similar to the Temperzone OSA950RKTBGV

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Actron Air CRV85AT / EVA85AT86 kW heating85 kW cooling21,698 kWh/yr2.5$6,943
Actron Air CRV850T / EVA850T86 kW heating85 kW cooling24,237 kWh/yr2.5$7,756
APAC S085OVR3SA/S085IHR3SA-TR80.8 kW heating84.1 kW cooling10,747 kWh/yr1.5$3,439
APAC S085OVR3SA- / S085IHR3SA--XR80.8 kW heating84.1 kW cooling10,747 kWh/yr1.5$3,439

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OSA840RKTBGV/ISD840KBXH-P78.3 kW heating81.3 kW cooling10,568 kWh/yr1.5$3,382

Compare OSA950RKTBGV/ISD950KBXH-P with another model

Temperzone OSA950RKTBGV specifications

Type
Reverse cycle
Configuration
Split system
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
88.65 kW
Cooling power input
30.12 kW
Rated heating capacity (7 Β°C)
90.39 kW
Heating power input
26.61 kW
EER, full load (tested)
2.94
COP, full load (tested)
3.40
Rated AEER
2.94
Rated ACOP
3.39
Standby power (PIA)
22.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OSA950RKTBGV zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––19,223–
Coldresidential1.00.08,257–
Mixedcommercial––23,730–
Mixedresidential1.00.012,525–
Hotcommercial––51,414–
Hotresidential1.50.037,300–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

Australian GEMS registration details

Registration number
AAC6920
GEMS registration id
149619
Status
approved, available (self-reported)
Registration expires
30 September 2027
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
Simulation
MEPS
2020
Product class
Class 25

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.