c/kWh
Energy rating (cooling)
2
Heating: 1
Annual electricity use
13,739 kWh
1,826 cooling + 11,913 heating
Estimated running cost
$4,534 / year
$378 / month Β· $45,339 over 10 years
Capacity
23.8 kW cooling
24.3 kW heating

2% less electricity than the median of 17 comparable 25 kW reverse cycle ducted packaged registrations (14,025 kWh a year) in the cold zone. Uses less than 53% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 10% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

AIRSTAGE RAQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 13,739$4,534$45,339
Mixed zone 7,081$2,337$23,367
Hot zone 8,636$2,850$28,499

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 23.8 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Actron Air PRV22AT23 kW heating22 kW cooling10,306 kWh/yr2.5$3,401
APAC P020AHR3SA-RTR18.9 kW heating22.4 kW cooling11,029 kWh/yr1.5$3,640
APAC P020AHR3SA-RBB18.9 kW heating22.4 kW cooling11,029 kWh/yr1.5$3,640
Actron Air PRV25AT26 kW heating24.9 kW cooling11,953 kWh/yr2.5$3,944
Temperzone OPA242RKTB22 kW heating22.4 kW cooling12,564 kWh/yr1.5$4,146

Heat pumps similar to the AIRSTAGE RAQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
APAC P024AHR3SA-RTT20.4 kW heating23.4 kW cooling11,785 kWh/yr1$3,889
APAC P024AVR3SA-LTR20.4 kW heating23.4 kW cooling11,785 kWh/yr1$3,889
Temperzone OPA250RLTFPQ26.9 kW heating24.6 kW cooling13,358 kWh/yr2.5$4,408
Actron Air PCG233U23.6 kW heating22.9 kW cooling12,680 kWh/yr1.5$4,184
Actron Air PCG23323.6 kW heating22.9 kW cooling12,680 kWh/yr1.5$4,184
Temperzone OPA242RKTB22 kW heating22.4 kW cooling12,564 kWh/yr1.5$4,146

Other AIRSTAGE models of similar capacity

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/K/WP/11024.8 kW heating24.4 kW cooling14,357 kWh/yr1.5$4,738
AIRSTAGE RAQ/K/WP/* 11024.8 kW heating24.4 kW cooling14,357 kWh/yr1.5$4,738

Compare RAQ/IL/EC/WP/110 with another model

AIRSTAGE RAQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
23.80 kW
Cooling power input
6.20 kW
Rated heating capacity (7 Β°C)
24.30 kW
Heating power input
5.65 kW
EER, full load (tested)
3.94
COP, full load (tested)
4.32
Rated AEER
3.78
Rated ACOP
4.23
Standby power (PIA)
30.0 W
Compressor
Variable speed, Inverter
Refrigerant
R454B
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

AIRSTAGE RAQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,2023,981
Coldresidential2.01.01,82611,913
Mixedcommercial––5,1632,077
Mixedresidential2.01.52,7434,338
Hotcommercial––10,893462
Hotresidential2.01.57,926710
Part-load test points (18 values)
h__h2_ext_cap_power_rated
5880 W
h__h3_ext_cap_power_rated
2650 W
c__t1_half_cap_power_rated
3890 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
3840 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
Yes
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
17550 W
h__h3_ext_cap_heat_cap_rated
5800 W
h__h1_half_cap_heat_cap_rated
13350 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
13050 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC10450
GEMS registration id
180200
Status
approved, available (self-reported)
Registration expires
14 September 2031
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: fujitsugeneral.com.au. How the derived figures are calculated.