c/kWh
Energy rating (cooling)
1.5
Heating: 1
Annual electricity use
18,409 kWh
2,811 cooling + 15,598 heating
Estimated running cost
$6,075 / year
$506 / month Β· $60,750 over 10 years
Capacity
31.7 kW cooling
32.1 kW heating

490% more electricity than the median of 30 comparable 35 kW reverse cycle ducted packaged registrations (3,122 kWh a year) in the cold zone. Uses less than 30% of them.

Across all 3,612 air conditioner registrations sold in Australia, it uses less than 7% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

AIRSTAGE RAQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 18,409$6,075$60,750
Mixed zone 10,492$3,462$34,624
Hot zone 13,570$4,478$44,781

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 31.7 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P029AHR3SA-RTT30.1 kW heating31 kW cooling2,267 kWh/yr2$748
APAC P029AHR3SA-LTT30.1 kW heating31 kW cooling2,267 kWh/yr2$748
Caa VPA030R3AC33.1 kW heating32.1 kW cooling2,638 kWh/yr1.5$871
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling2,665 kWh/yr1.5$879
Actron Air PCG330U33 kW heating32 kW cooling2,779 kWh/yr1.5$917

Heat pumps similar to the AIRSTAGE RAQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Actron Air PCG330U33 kW heating32 kW cooling2,779 kWh/yr1.5$917
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling2,665 kWh/yr1.5$879
Caa VPA030R3AC33.1 kW heating32.1 kW cooling2,638 kWh/yr1.5$871
APAC P030AVR3SA-LTR26.5 kW heating32.1 kW cooling17,568 kWh/yr1.5$5,797
APAC P030AVR3SA-LTS26.5 kW heating32.1 kW cooling17,568 kWh/yr1.5$5,797
Actron Air PKV330T-L/R33.5 kW heating32.4 kW cooling2,912 kWh/yr1$961

Other AIRSTAGE models of similar capacity

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/K/EC/WP/ECO/11232.2 kW heating31.8 kW cooling18,239 kWh/yr1.5$6,019
AIRSTAGE RAQ/K/EC/WP/11232.2 kW heating31.8 kW cooling18,239 kWh/yr1.5$6,019

Compare RAQ/K/WP/112 with another model

AIRSTAGE RAQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
31.70 kW
Cooling power input
10.10 kW
Rated heating capacity (7 Β°C)
32.10 kW
Heating power input
9.80 kW
EER, full load (tested)
3.17
COP, full load (tested)
3.26
Rated AEER
3.12
Rated ACOP
3.25
Standby power (PIA)
20.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

AIRSTAGE RAQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,4855,307
Coldresidential1.51.02,81115,598
Mixedcommercial––7,9972,904
Mixedresidential1.51.04,2506,242
Hotcommercial––17,279641
Hotresidential1.51.012,5551,015
Part-load test points (4 values)
h__h2_full_cap_power_rated
9173 W
h__h3_have_full_cap_results
No
h__h2_full_cap_heat_cap_rated
27959 W
c__low_temp_have_full_cap_results
No

Other model numbers on registration AAC6550

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC6550
GEMS registration id
145013
Status
approved, available (self-reported)
Registration expires
7 March 2027
Registered for sale in
Australia, New Zealand
Family
RAQ/K/WP/* 112
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: fujitsugeneral.com.au. How the derived figures are calculated.