c/kWh
Energy rating (cooling)
3.5
Heating: 3
Annual electricity use
7,058 kWh
933 cooling + 6,125 heating
Estimated running cost
$2,329 / year
$194 / month Β· $23,291 over 10 years
Capacity
18.1 kW cooling
21.5 kW heating

8% less electricity than the median of 17 comparable 18 kW reverse cycle multi-split / vrf registrations (7,693 kWh a year) in the cold zone. Uses less than 53% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 24% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Aux ARV-H180 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 7,058$2,329$23,291
Mixed zone 3,741$1,235$12,345
Hot zone 4,606$1,520$15,200

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 18.1 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Smart User SMV-V170W/N117 kW heating17 kW cooling5,813 kWh/yr3.5$1,918
Silicon Electronics EMV-V170W/N117 kW heating17 kW cooling5,813 kWh/yr3.5$1,918
Smart User SMV-V170W/N117 kW heating17 kW cooling5,819 kWh/yr3.5$1,920
Silicon Electronics EMV-V200W/N120 kW heating18 kW cooling6,654 kWh/yr3.5$2,196
Daikin RXYMQ6BVM16 kW heating16 kW cooling6,754 kWh/yr2$2,229

Heat pumps similar to the Aux ARV-H180

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Hisense AVW-63HJFAH120 kW heating18.1 kW cooling7,693 kWh/yr3.5$2,539
Mdv MVI-180WV2GN1(A)20 kW heating18 kW cooling9,435 kWh/yr2$3,114
Smart User SMV-V225W/N122.5 kW heating18 kW cooling6,661 kWh/yr4.5$2,198
Smart User SMV-V200W/N120 kW heating18 kW cooling6,654 kWh/yr3.5$2,196
Silicon Electronics EMV-V200W/N120 kW heating18 kW cooling6,654 kWh/yr3.5$2,196
Midea MVI-180WV2GN1(A)20 kW heating18 kW cooling9,435 kWh/yr2$3,114
Midea MV8M-180WV2N819.5 kW heating17.5 kW cooling8,649 kWh/yr2.5$2,854
Actron Air MMV-180CS19.5 kW heating17.5 kW cooling8,649 kWh/yr2.5$2,854

Compare ARV-H180/NR1B-AU with another model

Aux ARV-H180 specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
18.10 kW
Cooling power input
4.50 kW
Rated heating capacity (7 Β°C)
21.50 kW
Heating power input
5.20 kW
EER, full load (tested)
3.89
COP, full load (tested)
3.94
Rated AEER
3.98
Rated ACOP
4.10
Standby power (PIA)
14.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Single phase
Indoor sound power
–
Outdoor sound power
69.4 dB(A)
Demand response (AS/NZS 4755)
No
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Aux ARV-H180 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––2,0301,955
Coldresidential3.53.09336,125
Mixedcommercial––2,5631,022
Mixedresidential3.53.51,4652,276
Hotcommercial––5,706222
Hotresidential4.04.04,264342
Part-load test points (18 values)
h__h1_min_cap_power_rated
1450 W
h__h2_ext_cap_power_rated
4530 W
c__t1_half_cap_power_rated
1650 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
1580 W
h__h1_have_min_cap_results
Yes
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_min_cap_heat_cap_rated
8860 W
h__h2_ext_cap_heat_cap_rated
19300 W
h__h1_half_cap_heat_cap_rated
11000 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
9300 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC8858
GEMS registration id
169493
Status
approved, available (self-reported)
Registration expires
18 May 2030
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 20

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: auxcac.cn. How the derived figures are calculated.