c/kWh
Energy rating (cooling)
2.5
Heating: 1
Annual electricity use
21,235 kWh
2,002 cooling + 19,233 heating
Estimated running cost
$7,008 / year
$584 / month Β· $70,076 over 10 years
Capacity
33.5 kW cooling
37.5 kW heating

7% more electricity than the median of 23 comparable 35 kW reverse cycle multi-split / vrf registrations (19,794 kWh a year) in the cold zone. Uses less than 30% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 6% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Daikin REYQ12BYM9 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 21,235$7,008$70,076
Mixed zone 9,859$3,253$32,535
Hot zone 9,504$3,136$31,363

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 33.5 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Carrier 38VT012188QTSG33.5 kW heating33.5 kW cooling1,540 kWh/yr4.5$508
Toshiba MMY-MUP1201HT8P-A37.5 kW heating33.5 kW cooling1,782 kWh/yr3$588
Carrier 38VT012188HTSG37.5 kW heating33.5 kW cooling1,782 kWh/yr3$588
Toshiba MMY-MAP1206FT8P-A33.5 kW heating33.5 kW cooling2,404 kWh/yr1.5$793
Hisense AVWT-114FKFSHA33.5 kW heating33.5 kW cooling14,371 kWh/yr2.5$4,742

Heat pumps similar to the Daikin REYQ12BYM9

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Mdv MV8-335WV2RN1E(MA)33.5 kW heating33.5 kW cooling20,279 kWh/yr2$6,692
Toshiba MMY-MUP1201HT8P-A37.5 kW heating33.5 kW cooling1,782 kWh/yr3$588
Toshiba MMY-MAP1206FT8P-A33.5 kW heating33.5 kW cooling2,404 kWh/yr1.5$793
Hisense AVWT-114FKFSHA33.5 kW heating33.5 kW cooling14,371 kWh/yr2.5$4,742
Carrier 38VT012188HTSG37.5 kW heating33.5 kW cooling1,782 kWh/yr3$588
Carrier 38VT012188QTSG33.5 kW heating33.5 kW cooling1,540 kWh/yr4.5$508
Mitsubishi Heavy Industries FDC335KXZME1A33.5 kW heating33.5 kW cooling15,441 kWh/yr2$5,096
Fujitsu AJY108LELBH33.5 kW heating33.5 kW cooling18,222 kWh/yr2.5$6,013

Compare REYQ12BYM9 with another model

Daikin REYQ12BYM9 specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
33.50 kW
Cooling power input
9.02 kW
Rated heating capacity (7 Β°C)
37.50 kW
Heating power input
10.13 kW
EER, full load (tested)
3.49
COP, full load (tested)
3.54
Rated AEER
3.61
Rated ACOP
3.61
Standby power (PIA)
78.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Daikin REYQ12BYM9 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,7325,886
Coldresidential2.51.02,00219,233
Mixedcommercial––4,8822,814
Mixedresidential2.51.53,0756,784
Hotcommercial––10,988638
Hotresidential3.52.58,544960
Part-load test points (20 values)
h__h2_ext_cap_power_rated
13318 W
c__t1_half_cap_power_rated
3393 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
4202 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
26352 W
h__h1_half_cap_heat_cap_rated
18750 W
h__h2_is_capable_extended_load
Yes
c__low_temp_full_cap_power_rated
8246.108 W
c__low_temp_half_cap_power_rated
2714 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
16750 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_full_cap_cooling_cap_rated
36079.5 W
c__low_temp_half_cap_cooling_cap_rated
16750 W

New Zealand E3 registration details

Registration number
AAC7285
GEMS registration id
152761
Status
approved, available (self-reported)
Registration expires
27 February 2028
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 20

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: daikin.com.au. How the derived figures are calculated.