New Zealand Β· costs in NZD

Reverse cycle multi-split / vrf air conditioner
Hitachi RAS-080RNCCLW Heat Pump
Hitachi RAS-080RNCCLW is a 22.4 kW reverse cycle multi-split / vrf heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC7322).
- Energy rating (cooling)
- 2
- Heating: 2
- Annual electricity use
- 9,894 kWh
- 1,394 cooling + 8,500 heating
- Estimated running cost
- $3,265 / year
- $272 / month Β· $32,650 over 10 years
- Capacity
- 22.4 kW cooling
- 25 kW heating
2% less electricity than the median of 29 comparable 20 kW reverse cycle multi-split / vrf registrations (10,056 kWh a year) in the cold zone. Uses less than 55% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 14% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Hitachi RAS-080RNCCLW running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 9,894 | $3,265 | $32,650 |
| Mixed zone | 5,154 | $1,701 | $17,008 |
| Hot zone | 5,807 | $1,916 | $19,163 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 22.4 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Daikin RSUYA7AYM22.4 kW heating20 kW cooling7,360 kWh/yr | 3 | $2,429 | |
| Panasonic U-8MF3R725 kW heating22.4 kW cooling8,140 kWh/yr | 4 | $2,686 | |
| Daikin RSUYA8AYM25 kW heating22.4 kW cooling8,492 kWh/yr | 3 | $2,802 | |
| Mitsubishi Heavy Industries FDC224KXZPE122.4 kW heating22.4 kW cooling8,641 kWh/yr | 2.5 | $2,852 | |
| Mitsubishi Heavy Industries FDC224KXZME122.4 kW heating22.4 kW cooling8,706 kWh/yr | 2.5 | $2,873 |
Heat pumps similar to the Hitachi RAS-080RNCCLW
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Toshiba MMY-MUP0801FT8P-A22.4 kW heating22.4 kW cooling9,948 kWh/yr | 4 | $3,283 | |
| Daikin RSUYA8AYM25 kW heating22.4 kW cooling8,492 kWh/yr | 3 | $2,802 | |
| Toshiba MMY-MUP08S1HT8P-A25 kW heating22.4 kW cooling9,472 kWh/yr | 3 | $3,126 | |
| Daikin REYA8AYM25 kW heating22.4 kW cooling9,254 kWh/yr | 3 | $3,054 | |
| Panasonic U-8LZ2E825 kW heating22.4 kW cooling9,522 kWh/yr | 2.5 | $3,142 | |
| Mitsubishi Heavy Industries FDC224KXZPE122.4 kW heating22.4 kW cooling8,641 kWh/yr | 2.5 | $2,852 | |
| Panasonic U-8MF3R725 kW heating22.4 kW cooling8,140 kWh/yr | 4 | $2,686 | |
| Mitsubishi Heavy Industries FDC224KXZME122.4 kW heating22.4 kW cooling8,706 kWh/yr | 2.5 | $2,873 |
Compare RAS-080RNCCLW with another model
Hitachi RAS-080RNCCLW specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 22.40 kW
- Cooling power input
- 4.53 kW
- Rated heating capacity (7 Β°C)
- 25.00 kW
- Heating power input
- 5.32 kW
- EER, full load (tested)
- 5.13
- COP, full load (tested)
- 4.93
- Rated AEER
- 4.56
- Rated ACOP
- 4.38
- Standby power (PIA)
- 114.5 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- 74.2 dB(A)
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- China
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Hitachi RAS-080RNCCLW zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 2,674 | 2,807 |
| Coldresidential | residential | 2.0 | 2.0 | 1,394 | 8,500 |
| Mixedcommercial | commercial | β | β | 3,261 | 1,447 |
| Mixedresidential | residential | 2.5 | 3.0 | 2,035 | 3,119 |
| Hotcommercial | commercial | β | β | 6,765 | 464 |
| Hotresidential | residential | 3.5 | 4.0 | 5,152 | 655 |
Part-load test points (16 values)
- h__h2_ext_cap_power_rated
- 5420 W
- c__t1_half_cap_power_rated
- 1930 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 2020 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 18680 W
- h__h1_half_cap_heat_cap_rated
- 12500 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 11200 W
- c__low_temp_have_half_cap_results
- No
New Zealand E3 registration details
- Registration number
- AAC7322
- GEMS registration id
- 151033
- Status
- approved, available (self-reported)
- Registration expires
- 1 March 2028
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 20
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: temperzone.com. How the derived figures are calculated.