New Zealand Β· costs in NZD

Reverse cycle multi-split / vrf air conditioner
Mitsubishi Electric PURY-EP300YNW-A1-BS Heat Pump
Mitsubishi Electric PURY-EP300YNW-A1-BS is a 33.5 kW reverse cycle multi-split / vrf heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC9255).
- Energy rating (cooling)
- 2.5
- Heating: 0
- Annual electricity use
- 34,368 kWh
- 2,127 cooling + 32,241 heating
- Estimated running cost
- $11,341 / year
- $945 / month Β· $113,414 over 10 years
- Capacity
- 33.5 kW cooling
- 37.5 kW heating
105% more electricity than the median of 20 comparable 35 kW reverse cycle multi-split / vrf registrations (16,791 kWh a year) in the cold zone. Uses less than 5% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Mitsubishi Electric PURY-EP300YNW-A1-BS running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 34,368 | $11,341 | $113,414 |
| Mixed zone | 15,615 | $5,153 | $51,530 |
| Hot zone | 10,300 | $3,399 | $33,990 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 33.5 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Panasonic U-12MF3R737.5 kW heating33.5 kW cooling1,731 kWh/yr | 3.5 | $571 | |
| Toshiba MMY-MUP12S1HT8P-A37.5 kW heating33.5 kW cooling1,925 kWh/yr | 3 | $635 | |
| Mitsubishi Electric PUHY-M300YXM-A-BS33.5 kW heating33.5 kW cooling2,700 kWh/yr | 1.5 | $891 | |
| Mitsubishi Electric PUHY-M300YXM series33.5 kW heating33.5 kW cooling2,700 kWh/yr | 1.5 | $891 | |
| Hitachi RAS-120RNCBLW37.5 kW heating33.5 kW cooling14,771 kWh/yr | 2 | $4,874 |
Heat pumps similar to the Mitsubishi Electric PURY-EP300YNW-A1-BS
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Panasonic U-12MF3R737.5 kW heating33.5 kW cooling1,731 kWh/yr | 3.5 | $571 | |
| Hitachi RAS-120RNCBLW37.5 kW heating33.5 kW cooling14,771 kWh/yr | 2 | $4,874 | |
| Toshiba MMY-MUP12S1HT8P-A37.5 kW heating33.5 kW cooling1,925 kWh/yr | 3 | $635 | |
| Toshiba MMY-MUP1201FT8P-A33.5 kW heating33.5 kW cooling16,127 kWh/yr | 4 | $5,322 | |
| Hitachi RAS-120HNCELW37.5 kW heating33.5 kW cooling15,666 kWh/yr | 2.5 | $5,170 | |
| Mitsubishi Heavy Industries FDC335KXZE3(A)33.5 kW heating33.5 kW cooling16,435 kWh/yr | 3 | $5,424 | |
| Mitsubishi Heavy Industries FDC335KXZRE233.5 kW heating33.5 kW cooling16,292 kWh/yr | 2.5 | $5,376 | |
| Daikin REYA12AYM37.5 kW heating33.5 kW cooling15,260 kWh/yr | 2.5 | $5,036 |
Compare PURY-EP300YNW-A1-BS with another model
Mitsubishi Electric PURY-EP300YNW-A1-BS specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 33.50 kW
- Cooling power input
- 8.66 kW
- Rated heating capacity (7 Β°C)
- 37.50 kW
- Heating power input
- 10.80 kW
- EER, full load (tested)
- 3.87
- COP, full load (tested)
- 3.78
- Rated AEER
- 3.77
- Rated ACOP
- 3.40
- Standby power (PIA)
- 69.5 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- Thailand
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Mitsubishi Electric PURY-EP300YNW-A1-BS zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 3,994 | 8,727 |
| Coldresidential | residential | 2.5 | 0.0 | 2,127 | 32,241 |
| Mixedcommercial | commercial | β | β | 5,242 | 4,073 |
| Mixedresidential | residential | 2.5 | 0.0 | 3,227 | 12,388 |
| Hotcommercial | commercial | β | β | 11,670 | 726 |
| Hotresidential | residential | 3.0 | 1.0 | 9,046 | 1,254 |
Part-load test points (18 values)
- h__h2_ext_cap_power_rated
- 10310 W
- c__t1_half_cap_power_rated
- 4030 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 4720 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 16300 W
- h__h1_half_cap_heat_cap_rated
- 18700 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_half_cap_power_rated
- 3160 W
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 16750 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_half_cap_cooling_cap_rated
- 16750 W
Other model numbers on registration AAC9255
Registered together and sharing the same test results. Usually variants of the same unit.
New Zealand E3 registration details
- Registration number
- AAC9255
- GEMS registration id
- 172054
- Status
- approved, available (self-reported)
- Registration expires
- 20 August 2030
- Registered for sale in
- Australia, New Zealand
- Family
- PURY-EP300YNW-A1 Series
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 20