c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
62,386 kWh
3,580 cooling + 58,806 heating
Estimated running cost
$20,587 / year
$1,716 / month Β· $205,874 over 10 years
Capacity
56 kW cooling
63 kW heating

124% more electricity than the median of 42 comparable 50 kW reverse cycle multi-split / vrf registrations (27,808 kWh a year) in the cold zone. Uses less than 2% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Mitsubishi Electric PURY-EP500YNW-A1-BS running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 62,386$20,587$205,874
Mixed zone 28,733$9,482$94,819
Hot zone 17,990$5,937$59,367

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 56 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling3,416 kWh/yr2.5$1,127
Toshiba MMY-MUP18S1HT8P-A54 kW heating50.4 kW cooling3,445 kWh/yr2$1,137
Mitsubishi Electric PUHY-M450YXM-A-BS50 kW heating50 kW cooling4,359 kWh/yr1.5$1,438
Mitsubishi Electric PUHY-M450YXM-A50 kW heating50 kW cooling4,359 kWh/yr1.5$1,438
Hitachi RAS-180RNCBLW56 kW heating50.4 kW cooling23,594 kWh/yr2$7,786

Heat pumps similar to the Mitsubishi Electric PURY-EP500YNW-A1-BS

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling3,416 kWh/yr2.5$1,127
Daikin REYQ20TAY163 kW heating56 kW cooling43,145 kWh/yr2$14,238
Mitsubishi Heavy Industries FDC560KXZE263 kW heating56 kW cooling33,546 kWh/yr2.5$11,070
Hitachi RAS-200RNCBLW63 kW heating56 kW cooling27,407 kWh/yr2$9,044
Daikin REYA20AYM63 kW heating56 kW cooling26,302 kWh/yr3$8,680
Hitachi RAS-200RNCCLW63 kW heating56 kW cooling31,030 kWh/yr2$10,240
Toshiba MMY-MUP2001FT8P-A56 kW heating56 kW cooling33,962 kWh/yr3$11,207

Other Mitsubishi Electric models of similar capacity

ModelStarsEst. cost / yrCompare
Mitsubishi Electric PUHY-M500YXM-A56 kW heating56 kW cooling5,377 kWh/yr1$1,774

Compare PURY-EP500YNW-A1-BS with another model

Mitsubishi Electric PURY-EP500YNW-A1-BS specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
56.00 kW
Cooling power input
15.30 kW
Rated heating capacity (7 Β°C)
63.00 kW
Heating power input
18.30 kW
EER, full load (tested)
3.67
COP, full load (tested)
3.56
Rated AEER
3.59
Rated ACOP
3.39
Standby power (PIA)
87.8 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PURY-EP500YNW-A1-BS zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––7,08915,685
Coldresidential2.50.03,58058,806
Mixedcommercial––9,1807,729
Mixedresidential2.50.05,48423,249
Hotcommercial––20,5021,348
Hotresidential3.01.015,6602,330
Part-load test points (18 values)
h__h2_ext_cap_power_rated
13850 W
c__t1_half_cap_power_rated
6620 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
7890 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
23300 W
h__h1_half_cap_heat_cap_rated
31500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
5360 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
28000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
28000 W

Other model numbers on registration AAC9234

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC9234
GEMS registration id
172059
Status
approved, available (self-reported)
Registration expires
19 August 2030
Registered for sale in
Australia, New Zealand
Family
PURY-EP500YNW-A1 Series
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.