c/kWh
Energy rating (cooling)
2
Heating: 1.5
Annual electricity use
30,883 kWh
5,193 cooling + 25,690 heating
Estimated running cost
$10,191 / year
$849 / month Β· $101,914 over 10 years
Capacity
67.2 kW cooling
67.2 kW heating

Only 2 comparable registrations in this cohort, so no percentile is shown.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 4% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Samsung Electronics AM240MXVGNR running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 30,883$10,191$101,914
Mixed zone 17,208$5,679$56,786
Hot zone 24,729$8,161$81,606

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps similar to the Samsung Electronics AM240MXVGNR

Technically comparable registrations: same configuration and type, capacity within 12%.

No comparable registrations from other brands.

Other Samsung Electronics models of similar capacity

ModelStarsEst. cost / yrCompare
Samsung Electronics AM240KXVAGH/EU75.6 kW heating67.2 kW cooling37,579 kWh/yr2$12,401
Samsung Electronics AM260MXVGNR/ET72.8 kW heating72.8 kW cooling34,270 kWh/yr1.5$11,309

Compare AM240MXVGNR/ET with another model

Samsung Electronics AM240MXVGNR specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
67.20 kW
Cooling power input
22.51 kW
Rated heating capacity (7 Β°C)
67.20 kW
Heating power input
17.10 kW
EER, full load (tested)
3.14
COP, full load (tested)
4.11
Rated AEER
2.95
Rated ACOP
3.87
Standby power (PIA)
82.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Samsung Electronics AM240MXVGNR zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––11,4317,824
Coldresidential2.01.55,19325,690
Mixedcommercial––14,2843,927
Mixedresidential1.52.58,0179,191
Hotcommercial––31,481888
Hotresidential2.03.023,3441,385
Part-load test points (20 values)
h__h1_min_cap_power_rated
2050 W
h__h2_ext_cap_power_rated
20580 W
c__t1_half_cap_power_rated
9360 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
7120 W
h__h1_have_min_cap_results
Yes
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_min_cap_heat_cap_rated
10080 W
h__h2_ext_cap_heat_cap_rated
53800 W
h__h1_half_cap_heat_cap_rated
33600 W
h__h2_is_capable_extended_load
Yes
c__low_temp_min_cap_power_rated
3600 W
c__low_temp_have_min_cap_results
Yes
c__t1_half_cap_cooling_cap_rated
33600 W
c__low_temp_have_half_cap_results
No
c__low_temp_min_cap_cooling_cap_rated
13440 W

New Zealand E3 registration details

Registration number
AAC6971
GEMS registration id
144645
Status
approved, available (self-reported)
Registration expires
30 September 2027
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.4:2012
MEPS
2020
Product class
Class 27

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. How the derived figures are calculated.