c/kWh
Energy rating (cooling)
1.5
Heating: 1
Annual electricity use
108,324 kWh
16,227 cooling + 92,097 heating
Estimated running cost
$35,747 / year
$2,979 / month Β· $357,469 over 10 years
Capacity
193.8 kW cooling
194.7 kW heating

161% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 4% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Temperzone OPA 2110RLTM1FDPQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 108,324$35,747$357,469
Mixed zone 61,463$20,283$202,828
Hot zone 79,129$26,113$261,126

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 193.8 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P170AHR3SA-CBR164.5 kW heating173.9 kW cooling15,426 kWh/yr1$5,091
APAC P170AHR3SA-CTR164.5 kW heating173.9 kW cooling15,426 kWh/yr1$5,091
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling15,908 kWh/yr1.5$5,250
Temperzone FPA1700RKTMGQ-P182.1 kW heating182.9 kW cooling16,967 kWh/yr1.5$5,599
Actron Air PKV2000T180.4 kW heating187.5 kW cooling17,310 kWh/yr1$5,712

Heat pumps similar to the Temperzone OPA 2110RLTM1FDPQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
AIRSTAGE URT/EC/WP/MS/172/SK208 kW heating195 kW cooling104,196 kWh/yr1.5$34,385
AIRSTAGE URT-EC-WP-MS-172-SK208 kW heating195 kW cooling104,196 kWh/yr1.5$34,385
Actron Air PKV2000T180.4 kW heating187.5 kW cooling17,310 kWh/yr1$5,712
Carrier 50FC-180190 kW heating181 kW cooling123,455 kWh/yr1.5$40,740
APAC P200AHR3SA-CBR194.4 kW heating209 kW cooling17,760 kWh/yr1.5$5,861
APAC P200AHR3SA-194.4 kW heating209 kW cooling17,760 kWh/yr1.5$5,861

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA2000RKTMG-P186.1 kW heating183.6 kW cooling17,006 kWh/yr1.5$5,612
Temperzone FPA1700RKTMGQ-P182.1 kW heating182.9 kW cooling16,967 kWh/yr1.5$5,599

Compare OPA 2110RLTM1FDPQ with another model

Temperzone OPA 2110RLTM1FDPQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
193.81 kW
Cooling power input
64.53 kW
Rated heating capacity (7 Β°C)
194.71 kW
Heating power input
55.23 kW
EER, full load (tested)
3.00
COP, full load (tested)
3.53
Rated AEER
3.00
Rated ACOP
3.52
Standby power (PIA)
41.5 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA 2110RLTM1FDPQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––33,39231,593
Coldresidential1.51.016,22792,097
Mixedcommercial––43,57717,341
Mixedresidential1.51.024,81336,650
Hotcommercial––96,7243,703
Hotresidential1.51.073,2925,837
Part-load test points (18 values)
h__h2_ext_cap_power_rated
60675 W
c__t1_half_cap_power_rated
37498 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
32855 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
169725 W
h__h1_half_cap_heat_cap_rated
100778 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
30170 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
98772 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
103574 W

New Zealand E3 registration details

Registration number
AAC7757
GEMS registration id
156345
Status
approved, available (self-reported)
Registration expires
3 September 2028
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24