c/kWh
Energy rating (cooling)
2.5
Heating: 1
Annual electricity use
92,691 kWh
12,114 cooling + 80,577 heating
Estimated running cost
$30,588 / year
$2,549 / month Β· $305,880 over 10 years
Capacity
177.9 kW cooling
184.1 kW heating

123% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 13% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Temperzone OPA1710RLTM4FDPQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 92,691$30,588$305,880
Mixed zone 49,570$16,358$163,581
Hot zone 60,394$19,930$199,300

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 177.9 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P150AHR3SA-CBR146.6 kW heating156.7 kW cooling13,252 kWh/yr1.5$4,373
APAC P150AHR3SA-146.6 kW heating156.7 kW cooling13,252 kWh/yr1.5$4,373
Daikin UAXYA170NY1170 kW heating170 kW cooling15,866 kWh/yr1$5,236
Daikin UAXYA170RY1170 kW heating170 kW cooling15,866 kWh/yr1$5,236
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling15,908 kWh/yr1.5$5,250

Heat pumps similar to the Temperzone OPA1710RLTM4FDPQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Carrier 50FC-180 R454b184 kW heating176 kW cooling128,718 kWh/yr1.5$42,477
Carrier 50FC-180190 kW heating181 kW cooling123,455 kWh/yr1.5$40,740
APAC P170AHR3SA-CTR164.5 kW heating173.9 kW cooling15,426 kWh/yr1$5,091
APAC P170AHR3SA-CBR164.5 kW heating173.9 kW cooling15,426 kWh/yr1$5,091
Daikin UAXYA170RY1170 kW heating170 kW cooling15,866 kWh/yr1$5,236
Daikin UAXYA170NY1170 kW heating170 kW cooling15,866 kWh/yr1$5,236

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling15,908 kWh/yr1.5$5,250
Temperzone FPA1700RKTMGQ-P182.1 kW heating182.9 kW cooling16,967 kWh/yr1.5$5,599

Compare OPA1710RLTM4FDPQ with another model

Temperzone OPA1710RLTM4FDPQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
177.92 kW
Cooling power input
58.06 kW
Rated heating capacity (7 Β°C)
184.06 kW
Heating power input
56.72 kW
EER, full load (tested)
3.06
COP, full load (tested)
3.25
Rated AEER
3.06
Rated ACOP
3.24
Standby power (PIA)
46.0 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
–
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA1710RLTM4FDPQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––24,09326,102
Coldresidential2.51.012,11480,577
Mixedcommercial––31,85813,783
Mixedresidential2.01.518,98430,586
Hotcommercial––72,5882,840
Hotresidential2.52.055,8964,498
Part-load test points (18 values)
h__h2_ext_cap_power_rated
67779 W
c__t1_half_cap_power_rated
26120 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
24640 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
165732 W
h__h1_half_cap_heat_cap_rated
94513 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
21600 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
87800 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
99320 W

New Zealand E3 registration details

Registration number
AAC8002
GEMS registration id
158739
Status
approved, available (self-reported)
Registration expires
14 January 2029
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.