New Zealand Β· costs in NZD

Reverse cycle outdoor unit only air conditioner
Temperzone OSA 352RLTFV Heat Pump
Temperzone OSA 352RLTFV is a 31.5 kW reverse cycle ducted outdoor unit only heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC9865).
- Energy rating (cooling)
- 1.5
- Heating: 1.5
- Annual electricity use
- 16,096 kWh
- 2,520 cooling + 13,576 heating
- Estimated running cost
- $5,312 / year
- $443 / month Β· $53,117 over 10 years
- Capacity
- 31.5 kW cooling
- 31.3 kW heating
Only 1 comparable registration in this cohort, so no percentile is shown.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 8% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Temperzone OSA 352RLTFV running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 16,096 | $5,312 | $53,117 |
| Mixed zone | 8,881 | $2,931 | $29,307 |
| Hot zone | 12,104 | $3,994 | $39,943 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps similar to the Temperzone OSA 352RLTFV
Technically comparable registrations: same configuration and type, capacity within 12%.
No comparable registrations from other brands.
Compare OSA 352RLTFV with another model
Temperzone OSA 352RLTFV specifications
- Type
- Reverse cycle
- Configuration
- Outdoor unit only
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 31.48 kW
- Cooling power input
- 10.02 kW
- Rated heating capacity (7 Β°C)
- 31.29 kW
- Heating power input
- 9.31 kW
- EER, full load (tested)
- 3.14
- COP, full load (tested)
- 3.36
- Rated AEER
- 3.13
- Rated ACOP
- 3.35
- Standby power (PIA)
- 11.8 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R32
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- New Zealand, Australia
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Temperzone OSA 352RLTFV zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 6,504 | 4,126 |
| Coldresidential | residential | 1.5 | 1.5 | 2,520 | 13,576 |
| Mixedcommercial | commercial | β | β | 7,849 | 2,108 |
| Mixedresidential | residential | 1.5 | 1.5 | 3,906 | 4,975 |
| Hotcommercial | commercial | β | β | 15,961 | 416 |
| Hotresidential | residential | 2.0 | 2.5 | 11,443 | 661 |
Part-load test points (25 values)
- c__t1_min_cap_power_rated
- 3700 W
- h__h1_min_cap_power_rated
- 2700 W
- h__h2_ext_cap_power_rated
- 11000 W
- c__t1_half_cap_power_rated
- 4400 W
- c__t1_have_min_cap_results
- Yes
- h__h1_half_cap_power_rated
- 3600 W
- h__h1_have_min_cap_results
- Yes
- h__h2_full_cap_power_rated
- 8900 W
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- Yes
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h1_min_cap_heat_cap_rated
- 12000 W
- h__h2_ext_cap_heat_cap_rated
- 26500 W
- h__h1_half_cap_heat_cap_rated
- 15700 W
- h__h2_full_cap_heat_cap_rated
- 22400 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_min_cap_power_rated
- 3300 W
- c__t1_min_cap_cooling_cap_rated
- 12100 W
- c__low_temp_half_cap_power_rated
- 4100 W
- c__t1_half_cap_cooling_cap_rated
- 15900 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_min_cap_cooling_cap_rated
- 10700 W
- c__low_temp_half_cap_cooling_cap_rated
- 16500 W
New Zealand E3 registration details
- Registration number
- AAC9865
- GEMS registration id
- 176999
- Status
- approved, available (self-reported)
- Registration expires
- 12 February 2031
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- β
- Regulatory standard
- [SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2019
- Product class
- Class 16
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.