c/kWh
Energy rating (cooling)
1
Heating: 0
Annual electricity use
5,544 kWh
Estimated running cost
$1,774 / year
$148 / month Β· $17,741 over 10 years
Capacity
39.2 kW cooling
39.5 kW heating

3% less electricity than the median of 13 comparable 40 kW reverse cycle ducted packaged registrations (5,740 kWh a year) in the mixed zone. Uses less than 54% of them.

Across all 3,681 air conditioner registrations sold in Australia, it uses less than 15% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Actron Air PCG400L running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 3,697$1,183$11,830
Mixed zone 5,544$1,774$17,741
Hot zone 16,026$5,128$51,283

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 39.2 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P035AHR3SA-31.5 kW heating36 kW cooling3,796 kWh/yr2$1,215
APAC P035AHR3SA-LRR31.5 kW heating36 kW cooling3,796 kWh/yr2$1,215
Caa VPA035R3AC37.4 kW heating34.7 kW cooling4,325 kWh/yr1.5$1,384
Caa HPA035R3AD38.1 kW heating36.3 kW cooling4,367 kWh/yr1.5$1,397
Temperzone OPA370RKTB35.9 kW heating36.8 kW cooling4,793 kWh/yr1.5$1,534

Air conditioners similar to the Actron Air PCG400L

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
APAC P038AHR3SA-RBB37.7 kW heating39.7 kW cooling4,657 kWh/yr1.5$1,490
APAC P038AHR3SA-RRR37.7 kW heating39.7 kW cooling4,657 kWh/yr1.5$1,490
Daikin UAYN400AFY1A37.6 kW heating40.8 kW cooling16,674 kWh/yr1.5$5,336
Daikin UAYN350AFY1A34.3 kW heating37.2 kW cooling12,391 kWh/yr1.5$3,965
Temperzone OPA 371RLTP36.2 kW heating37 kW cooling11,695 kWh/yr1.5$3,742
Temperzone OPA370RKTB35.9 kW heating36.8 kW cooling4,793 kWh/yr1.5$1,534
Caa HPA035R3AD38.1 kW heating36.3 kW cooling4,367 kWh/yr1.5$1,397
AIRSTAGE RAQ/L/EC/WP/11533.9 kW heating36.2 kW cooling10,731 kWh/yr1.5$3,434

Compare PCG400L with another model

Actron Air PCG400L specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
39.20 kW
Cooling power input
12.76 kW
Rated heating capacity (7 Β°C)
39.50 kW
Heating power input
11.97 kW
EER, full load (tested)
2.97
COP, full load (tested)
3.26
Rated AEER
3.02
Rated ACOP
3.24
Standby power (PIA)
69.2 W
Compressor
Variable speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes (requires additional part)
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Actron Air PCG400L zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––8,330–
Coldresidential1.00.03,697–
Mixedcommercial––10,240–
Mixedresidential1.00.05,544–
Hotcommercial––21,963–
Hotresidential1.50.016,026–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

Other model numbers on registration AAC9956

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9956
GEMS registration id
177567
Status
approved, available (self-reported)
Registration expires
25 August 2031
Registered for sale in
Australia, New Zealand
Family
PCG400
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 7

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: actronair.com.au. How the derived figures are calculated.