c/kWh
Energy rating (cooling)
1.5
Heating: 0
Annual electricity use
4,367 kWh
Estimated running cost
$1,397 / year
$116 / month Β· $13,974 over 10 years
Capacity
36.3 kW cooling
38.1 kW heating

7% less electricity than the median of 30 comparable 35 kW reverse cycle ducted packaged registrations (4,705 kWh a year) in the mixed zone. Uses less than 60% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 21% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Caa HPA035R3AD running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 2,881$922$9,219
Mixed zone 4,367$1,397$13,974
Hot zone 12,987$4,156$41,558

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 36.3 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P033AHR3SA-LTT32.9 kW heating34.4 kW cooling3,778 kWh/yr2$1,209
APAC P033AHR3SA-RBB32.9 kW heating34.4 kW cooling3,778 kWh/yr2$1,209
Caa VPA030R3AC33.1 kW heating32.1 kW cooling3,998 kWh/yr1.5$1,279
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling4,041 kWh/yr1.5$1,293
Actron Air PCG330U33 kW heating32 kW cooling4,163 kWh/yr1.5$1,332

Air conditioners similar to the Caa HPA035R3AD

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/L/EC/WP/11533.9 kW heating36.2 kW cooling10,731 kWh/yr1.5$3,434
AIRSTAGE RAQ/K/EC/WP/*11536.3 kW heating36.2 kW cooling11,734 kWh/yr1.5$3,755
APAC P035AHR3SA-LRR31.5 kW heating36 kW cooling3,796 kWh/yr2$1,215
APAC P035AVR3SA-RTR31.5 kW heating36 kW cooling3,796 kWh/yr2$1,215
Temperzone OPA370RKTB35.9 kW heating36.8 kW cooling4,793 kWh/yr1.5$1,534
Temperzone OPA 371RLTP36.2 kW heating37 kW cooling11,695 kWh/yr1.5$3,742
Daikin UAYN350AFY1A34.3 kW heating37.2 kW cooling12,391 kWh/yr1.5$3,965
Daikin UAYQ120CY1A35.8 kW heating34.4 kW cooling11,548 kWh/yr1$3,695

Compare HPA035R3AD with another model

Caa HPA035R3AD specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
36.31 kW
Cooling power input
10.48 kW
Rated heating capacity (7 Β°C)
38.14 kW
Heating power input
9.91 kW
EER, full load (tested)
3.41
COP, full load (tested)
3.74
Rated AEER
3.45
Rated ACOP
3.84
Standby power (PIA)
10.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Caa HPA035R3AD zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,696–
Coldresidential2.00.02,881–
Mixedcommercial––8,264–
Mixedresidential1.50.04,367–
Hotcommercial––17,896–
Hotresidential2.00.012,987–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

Australian GEMS registration details

Registration number
AAC7352
GEMS registration id
153013
Status
approved, available (self-reported)
Registration expires
14 March 2028
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. How the derived figures are calculated.