c/kWh
Energy rating (cooling)
2
Heating: 0
Annual electricity use
3,796 kWh
Estimated running cost
$1,215 / year
$101 / month Β· $12,147 over 10 years
Capacity
36 kW cooling
31.5 kW heating

19% less electricity than the median of 30 comparable 35 kW reverse cycle ducted packaged registrations (4,705 kWh a year) in the mixed zone. Uses less than 87% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 25% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

APAC P035AHR3SA-LRR running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 2,497$799$7,990
Mixed zone 3,796$1,215$12,147
Hot zone 10,526$3,368$33,683

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners similar to the APAC P035AHR3SA-LRR

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/K/WP/11536.2 kW heating36.1 kW cooling11,865 kWh/yr1.5$3,797
AIRSTAGE RAQ/K/WP/ECO/11536.2 kW heating36.1 kW cooling11,865 kWh/yr1.5$3,797
Caa HPA035R3AD38.1 kW heating36.3 kW cooling4,367 kWh/yr1.5$1,397
Temperzone OPA370RKTB35.9 kW heating36.8 kW cooling4,793 kWh/yr1.5$1,534
Temperzone OPA 371RLTP36.2 kW heating37 kW cooling11,695 kWh/yr1.5$3,742
Daikin UAYN350AFY1A34.3 kW heating37.2 kW cooling12,391 kWh/yr1.5$3,965

Other APAC models of similar capacity

ModelStarsEst. cost / yrCompare
APAC P035AVR3SA-LTR31.5 kW heating36 kW cooling3,796 kWh/yr2$1,215
APAC P035AVR3SA-LTS31.5 kW heating36 kW cooling3,796 kWh/yr2$1,215

Compare P035AHR3SA-LRR with another model

APAC P035AHR3SA-LRR specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
36.00 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
31.50 kW
Heating power input
–
EER, full load (tested)
3.55
COP, full load (tested)
3.36
Rated AEER
3.59
Rated ACOP
3.41
Standby power (PIA)
100.0 W
Compressor
Variable speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

APAC P035AHR3SA-LRR zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––5,522–
Coldresidential2.00.02,497–
Mixedcommercial––6,752–
Mixedresidential2.00.03,796–
Hotcommercial––14,310–
Hotresidential2.50.010,526–
Part-load test points (8 values)
c__t1_min_cap_power_rated
4930 W
c__t1_have_min_cap_results
Yes
c__low_temp_min_cap_power_rated
4530 W
c__t1_min_cap_cooling_cap_rated
23550 W
c__low_temp_full_cap_power_rated
8760 W
c__low_temp_have_full_cap_results
Yes
c__low_temp_min_cap_cooling_cap_rated
24660 W
c__low_temp_full_cap_cooling_cap_rated
38410 W

Other model numbers on registration AAC7445

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC7445
GEMS registration id
–
Status
approved
Registration expires
24 April 2028
Registered for sale in
Australia, New Zealand
Family
P035AHR3SA-
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
Simulation
MEPS
2019
Product class
6

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. How the derived figures are calculated.