c/kWh
Energy rating (cooling)
1.5
Heating: 0
Annual electricity use
3,998 kWh
Estimated running cost
$1,279 / year
$107 / month Β· $12,794 over 10 years
Capacity
32.1 kW cooling
33.1 kW heating

15% less electricity than the median of 30 comparable 35 kW reverse cycle ducted packaged registrations (4,705 kWh a year) in the mixed zone. Uses less than 83% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 23% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Caa VPA030R3AC running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 2,638$844$8,442
Mixed zone 3,998$1,279$12,794
Hot zone 11,882$3,802$38,022

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 32.1 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P029AHR3SA-LTR30.1 kW heating31 kW cooling3,461 kWh/yr2$1,108
APAC P029AHR3SA-LTT30.1 kW heating31 kW cooling3,461 kWh/yr2$1,108

Air conditioners similar to the Caa VPA030R3AC

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
APAC P030AVR3SA-26.5 kW heating32.1 kW cooling9,635 kWh/yr1.5$3,083
APAC P030AHR3SA-LTT26.5 kW heating32.1 kW cooling9,635 kWh/yr1.5$3,083
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling4,041 kWh/yr1.5$1,293
Actron Air PCG330U33 kW heating32 kW cooling4,163 kWh/yr1.5$1,332
Actron Air PKV330T-L/R33.5 kW heating32.4 kW cooling4,361 kWh/yr1.5$1,396
AIRSTAGE RAQ/K/EC/WP/11232.2 kW heating31.8 kW cooling10,388 kWh/yr1.5$3,324
AIRSTAGE RAQ/K/EC/WP/ECO/11232.2 kW heating31.8 kW cooling10,388 kWh/yr1.5$3,324
Temperzone OPA 331RLTP29.8 kW heating33 kW cooling10,333 kWh/yr1.5$3,307

Compare VPA030R3AC with another model

Caa VPA030R3AC specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
32.14 kW
Cooling power input
9.59 kW
Rated heating capacity (7 Β°C)
33.12 kW
Heating power input
9.00 kW
EER, full load (tested)
3.31
COP, full load (tested)
3.51
Rated AEER
3.34
Rated ACOP
3.67
Standby power (PIA)
10.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Caa VPA030R3AC zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,127–
Coldresidential1.50.02,638–
Mixedcommercial––7,562–
Mixedresidential1.50.03,998–
Hotcommercial––16,372–
Hotresidential2.00.011,882–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

Australian GEMS registration details

Registration number
AAC6870
GEMS registration id
148855
Status
approved, available (self-reported)
Registration expires
15 August 2027
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. How the derived figures are calculated.