c/kWh
Energy rating (cooling)
1.5
Heating: 1
Annual electricity use
10,333 kWh
4,230 cooling + 6,103 heating
Estimated running cost
$3,307 / year
$276 / month Β· $33,066 over 10 years
Capacity
33 kW cooling
29.8 kW heating

120% more electricity than the median of 30 comparable 35 kW reverse cycle ducted packaged registrations (4,705 kWh a year) in the mixed zone. Uses less than 33% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 8% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Temperzone OPA 331RLTP running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 18,426$5,896$58,963
Mixed zone 10,333$3,307$33,066
Hot zone 13,411$4,292$42,915

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 33 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P029AHR3SA-30.1 kW heating31 kW cooling3,461 kWh/yr2$1,108
APAC P029AHR3SA-RRR30.1 kW heating31 kW cooling3,461 kWh/yr2$1,108
Caa VPA030R3AC33.1 kW heating32.1 kW cooling3,998 kWh/yr1.5$1,279
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling4,041 kWh/yr1.5$1,293
Actron Air PCG330U33 kW heating32 kW cooling4,163 kWh/yr1.5$1,332

Air conditioners similar to the Temperzone OPA 331RLTP

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Actron Air PKV330T-T32.5 kW heating33 kW cooling4,385 kWh/yr1.5$1,403
APAC P032AHR3SA-L31.1 kW heating32.9 kW cooling4,371 kWh/yr1.5$1,399
APAC P032AHX3SA31.1 kW heating32.9 kW cooling4,371 kWh/yr1.5$1,399
Actron Air PCG340L34.7 kW heating33.1 kW cooling11,131 kWh/yr1.5$3,562
Caa VPA030R3AC33.1 kW heating32.1 kW cooling3,998 kWh/yr1.5$1,279
AIRSTAGE RAQ/L/EC/WP/11229.6 kW heating33.9 kW cooling9,914 kWh/yr1.5$3,172
AIRSTAGE RAQ/K/EC/WP/*11232.2 kW heating31.8 kW cooling10,388 kWh/yr1.5$3,324
Daikin UAYQ120CY1A35.8 kW heating34.4 kW cooling11,548 kWh/yr1$3,695

Compare OPA 331RLTP with another model

Temperzone OPA 331RLTP specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
33.01 kW
Cooling power input
10.05 kW
Rated heating capacity (7 Β°C)
29.83 kW
Heating power input
8.62 kW
EER, full load (tested)
3.28
COP, full load (tested)
3.46
Rated AEER
3.26
Rated ACOP
3.43
Standby power (PIA)
20.0 W
Compressor
Fixed speed
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA 331RLTP zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,4535,057
Coldresidential1.50.52,79715,629
Mixedcommercial––7,9572,680
Mixedresidential1.51.04,2306,103
Hotcommercial––17,194573
Hotresidential1.51.012,493918
Part-load test points (4 values)
h__h2_full_cap_power_rated
8175 W
h__h3_have_full_cap_results
No
h__h2_full_cap_heat_cap_rated
21522 W
c__low_temp_have_full_cap_results
No

Australian GEMS registration details

Registration number
AAC9964
GEMS registration id
176664
Status
approved, available (self-reported)
Registration expires
19 March 2031
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6