c/kWh
Energy rating (cooling)
1.5
Heating: 1.5
Annual electricity use
53,597 kWh
23,367 cooling + 30,230 heating
Estimated running cost
$17,151 / year
$1,429 / month Β· $171,510 over 10 years
Capacity
169 kW cooling
173 kW heating

106% more electricity than the median of 54 comparable 80 kW and above reverse cycle ducted packaged registrations (25,969 kWh a year) in the mixed zone. Uses less than 11% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

AIRSTAGE URT running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 91,451$29,264$292,643
Mixed zone 53,597$17,151$171,510
Hot zone 74,461$23,828$238,275

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 169 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
APAC P150AHR3SA-146.6 kW heating156.7 kW cooling19,505 kWh/yr1.5$6,242
APAC P150AHR3SA-CBR146.6 kW heating156.7 kW cooling19,505 kWh/yr1.5$6,242
Daikin UAXYA170RY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Daikin UAXYA170SY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Temperzone OPA2100RKTMDF-P186.7 kW heating178 kW cooling24,120 kWh/yr1.5$7,718

Air conditioners similar to the AIRSTAGE URT

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAXYA170RY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Daikin UAXYA170SY1170 kW heating170 kW cooling23,635 kWh/yr1$7,563
Temperzone OPA1710RLTM1FPQ170.7 kW heating164.2 kW cooling55,312 kWh/yr1.5$17,700
APAC P170AHR3SA-CBR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
APAC P170AHR3SA-CTR164.5 kW heating173.9 kW cooling22,808 kWh/yr1.5$7,299
Carrier 50FC-180 R454b184 kW heating176 kW cooling66,529 kWh/yr1.5$21,289
Temperzone OPA1710RLTM4FDPQ184.1 kW heating177.9 kW cooling49,570 kWh/yr2$15,862
Carrier 50FC-180190 kW heating181 kW cooling65,242 kWh/yr1.5$20,877

Compare URT/EC/WP/MS/152/SK with another model

AIRSTAGE URT specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
169.00 kW
Cooling power input
56.30 kW
Rated heating capacity (7 Β°C)
173.00 kW
Heating power input
47.80 kW
EER, full load (tested)
2.94
COP, full load (tested)
3.54
Rated AEER
3.00
Rated ACOP
3.61
Standby power (PIA)
30.0 W
Compressor
Variable speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Italy, Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

AIRSTAGE URT zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––35,89725,789
Coldresidential1.51.015,39676,055
Mixedcommercial––44,32214,018
Mixedresidential1.51.523,36730,230
Hotcommercial––96,0682,990
Hotresidential1.51.569,6794,782
Part-load test points (4 values)
h__h2_full_cap_power_rated
45900 W
h__h3_have_full_cap_results
No
h__h2_full_cap_heat_cap_rated
156000 W
c__low_temp_have_full_cap_results
No

Other model numbers on registration AAC9201

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9201
GEMS registration id
171807
Status
approved, available (self-reported)
Registration expires
6 August 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
URT/EC/WP/MS 152
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24