c/kWh
Energy rating (cooling)
2
Heating: 0
Annual electricity use
4,628 kWh
Estimated running cost
$1,481 / year
$123 / month Β· $14,810 over 10 years
Capacity
43 kW cooling
40.3 kW heating

19% less electricity than the median of 13 comparable 40 kW reverse cycle ducted packaged registrations (5,740 kWh a year) in the mixed zone. Uses less than 85% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 19% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

APAC P040AHR3SA-RBB running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 3,057$978$9,782
Mixed zone 4,628$1,481$14,810
Hot zone 13,035$4,171$41,712

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners similar to the APAC P040AHR3SA-RBB

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAYQ150CY1A43.1 kW heating42.8 kW cooling14,090 kWh/yr1.5$4,509
AIRSTAGE RAQ/K/WP/11843.6 kW heating43.3 kW cooling14,831 kWh/yr1$4,746
AIRSTAGE RAQ/K/WP/ECO/11843.6 kW heating43.3 kW cooling14,831 kWh/yr1$4,746
Temperzone OPA450RLTFPQ44.4 kW heating43.3 kW cooling13,416 kWh/yr2$4,293
Temperzone OPA465RKTB41.3 kW heating42.5 kW cooling6,103 kWh/yr1$1,953
Daikin UAYN400AFY1A37.6 kW heating40.8 kW cooling16,674 kWh/yr1.5$5,336

Other APAC models of similar capacity

ModelStarsEst. cost / yrCompare
APAC P040AVR3SA-LTR40.3 kW heating43 kW cooling4,628 kWh/yr2$1,481
APAC P040AVR3SA-RTS40.3 kW heating43 kW cooling4,628 kWh/yr2$1,481

Compare P040AHR3SA-RBB with another model

APAC P040AHR3SA-RBB specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
43.00 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
40.30 kW
Heating power input
–
EER, full load (tested)
3.62
COP, full load (tested)
3.67
Rated AEER
3.70
Rated ACOP
3.72
Standby power (PIA)
100.0 W
Compressor
Variable speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

APAC P040AHR3SA-RBB zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,990–
Coldresidential2.00.03,057–
Mixedcommercial––8,498–
Mixedresidential2.00.04,628–
Hotcommercial––17,885–
Hotresidential2.50.013,035–
Part-load test points (8 values)
c__t1_min_cap_power_rated
6170 W
c__t1_have_min_cap_results
Yes
c__low_temp_min_cap_power_rated
5710 W
c__t1_min_cap_cooling_cap_rated
27380 W
c__low_temp_full_cap_power_rated
10280 W
c__low_temp_have_full_cap_results
Yes
c__low_temp_min_cap_cooling_cap_rated
28700 W
c__low_temp_full_cap_cooling_cap_rated
45730 W

Other model numbers on registration AAC7444

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC7444
GEMS registration id
–
Status
approved
Registration expires
24 April 2028
Registered for sale in
Australia, New Zealand
Family
P040AHR3SA-
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
Simulation
MEPS
2019
Product class
7

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. How the derived figures are calculated.