Australia Β· costs in AUD

Reverse cycle multi-split / vrf air conditioner
Hitachi RAS-140RNCBLW Air Conditioner
Hitachi RAS-140RNCBLW is a 40 kW reverse cycle multi-split / vrf air conditioner registered under Australiaβs Energy Rating (GEMS) scheme (registration AAC7256).
- Energy rating (cooling)
- 2
- Heating: 2.5
- Annual electricity use
- 10,547 kWh
- 4,053 cooling + 6,494 heating
- Estimated running cost
- $3,375 / year
- $281 / month Β· $33,750 over 10 years
- Capacity
- 40 kW cooling
- 45 kW heating
About the same electricity as the median of 18 comparable 40 kW reverse cycle multi-split / vrf registrations (10,587 kWh a year) in the mixed zone. Uses less than 50% of them.
Across all 3,680 air conditioner registrations sold in Australia, it uses less than 7% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ 32c/kWh in AUD; change the price above to your tariff.
Hitachi RAS-140RNCBLW running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 20,084 | $6,427 | $64,269 |
| Mixed zone | 10,547 | $3,375 | $33,750 |
| Hot zone | 11,355 | $3,634 | $36,336 |
At 32c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Air conditioners that use less electricity
Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the mixed zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr | 2.5 | $1,254 | |
| Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr | 1.5 | $1,601 | |
| Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling5,003 kWh/yr | 1.5 | $1,601 | |
| Panasonic U-14MF3R745 kW heating40 kW cooling8,732 kWh/yr | 3 | $2,794 | |
| Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr | 2.5 | $3,039 |
Air conditioners similar to the Hitachi RAS-140RNCBLW
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling5,003 kWh/yr | 1.5 | $1,601 | |
| Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr | 2.5 | $1,254 | |
| Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling10,278 kWh/yr | 3.5 | $3,289 | |
| Panasonic U-14MF3R745 kW heating40 kW cooling8,732 kWh/yr | 3 | $2,794 | |
| Daikin REYA14AYM45 kW heating40 kW cooling10,627 kWh/yr | 2.5 | $3,401 | |
| Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr | 2.5 | $3,039 | |
| Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr | 1.5 | $1,601 | |
| Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling10,236 kWh/yr | 2.5 | $3,276 |
Compare RAS-140RNCBLW with another model
Hitachi RAS-140RNCBLW specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 40.00 kW
- Cooling power input
- 9.15 kW
- Rated heating capacity (7 Β°C)
- 45.00 kW
- Heating power input
- 10.37 kW
- EER, full load (tested)
- 4.14
- COP, full load (tested)
- 4.16
- Rated AEER
- 3.97
- Rated ACOP
- 3.99
- Standby power (PIA)
- 271.4 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- China
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Hitachi RAS-140RNCBLW zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 5,093 | 5,798 |
| Coldresidential | residential | 1.5 | 2.0 | 2,789 | 17,295 |
| Mixedcommercial | commercial | β | β | 6,208 | 3,060 |
| Mixedresidential | residential | 2.0 | 2.5 | 4,053 | 6,494 |
| Hotcommercial | commercial | β | β | 12,827 | 1,033 |
| Hotresidential | residential | 3.0 | 3.0 | 9,910 | 1,445 |
Part-load test points (16 values)
- h__h2_ext_cap_power_rated
- 11780 W
- c__t1_half_cap_power_rated
- 3470 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 4210 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 33780 W
- h__h1_half_cap_heat_cap_rated
- 22500 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 20000 W
- c__low_temp_have_half_cap_results
- No
Australian GEMS registration details
- Registration number
- AAC7256
- GEMS registration id
- 151028
- Status
- approved, available (self-reported)
- Registration expires
- 9 February 2028
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 21