c/kWh
Energy rating (cooling)
3
Heating: 3
Annual electricity use
8,732 kWh
3,490 cooling + 5,242 heating
Estimated running cost
$2,794 / year
$233 / month Β· $27,942 over 10 years
Capacity
40 kW cooling
45 kW heating

17% less electricity than the median of 18 comparable 40 kW reverse cycle multi-split / vrf registrations (10,587 kWh a year) in the mixed zone. Uses less than 78% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 9% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Panasonic U-14MF3R7 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 17,008$5,443$54,426
Mixed zone 8,732$2,794$27,942
Hot zone 10,563$3,380$33,802

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601

Air conditioners similar to the Panasonic U-14MF3R7

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling10,236 kWh/yr2.5$3,276
Hitachi RAS-140HNCELW45 kW heating40 kW cooling9,658 kWh/yr2.5$3,091
Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling10,278 kWh/yr3.5$3,289
Hitachi RAS-140RNCBLW45 kW heating40 kW cooling10,547 kWh/yr2$3,375
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr2.5$3,039
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601

Compare U-14MF3R7 with another model

Panasonic U-14MF3R7 specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
40.00 kW
Cooling power input
10.80 kW
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
10.70 kW
EER, full load (tested)
3.52
COP, full load (tested)
4.04
Rated AEER
3.60
Rated ACOP
4.09
Standby power (PIA)
91.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
80.4 dB(A)
Demand response (AS/NZS 4755)
Yes (mode 1 on off, mode 2 50 percent, mode 3 75 percent)
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Panasonic U-14MF3R7 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,5434,586
Coldresidential3.02.52,24114,767
Mixedcommercial––5,7392,328
Mixedresidential3.03.03,4905,242
Hotcommercial––12,732591
Hotresidential3.54.09,685878
Part-load test points (19 values)
h__h2_ext_cap_power_rated
13800 W
c__t1_half_cap_power_rated
3370 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
3540 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
38400 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_full_cap_power_rated
9871.2 W
c__low_temp_half_cap_power_rated
3080.1800000000003 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
20000 W
c__low_temp_have_half_cap_results
No
c__low_temp_full_cap_cooling_cap_rated
43080 W
c__low_temp_half_cap_cooling_cap_rated
21540 W

Australian GEMS registration details

Registration number
AAC7668
GEMS registration id
155661
Status
approved, available (self-reported)
Registration expires
2 August 2028
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.