c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
11,882 kWh
2,516 cooling + 9,366 heating
Estimated running cost
$3,802 / year
$317 / month Β· $38,022 over 10 years
Capacity
28 kW cooling
31.5 kW heating

75% more electricity than the median of 32 comparable 25 kW reverse cycle multi-split / vrf registrations (6,791 kWh a year) in the mixed zone. Uses less than 6% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 6% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-P250YNW-A1-BS running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 26,273$8,407$84,074
Mixed zone 11,882$3,802$38,022
Hot zone 7,944$2,542$25,421

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 28 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Panasonic U-10MF3R731.5 kW heating28 kW cooling5,199 kWh/yr4$1,664
Panasonic U-10LZ2E828 kW heating28 kW cooling5,879 kWh/yr2.5$1,881
Daikin REYA10AYM31.5 kW heating28 kW cooling6,052 kWh/yr3$1,937
Toshiba MMY-MUP1001FT8P-A28 kW heating28 kW cooling6,104 kWh/yr4$1,953
Toshiba MMY-MUP10S1HT8P-A31.5 kW heating28 kW cooling6,332 kWh/yr3$2,026

Air conditioners similar to the Mitsubishi Electric PUHY-P250YNW-A1-BS

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP10S1HT8P-A31.5 kW heating28 kW cooling6,332 kWh/yr3$2,026
Mitsubishi Heavy Industries FDC280KXZME128 kW heating28 kW cooling6,561 kWh/yr2.5$2,100
Panasonic U-10MF3R731.5 kW heating28 kW cooling5,199 kWh/yr4$1,664
Hitachi RAS-100RNCBLW31.5 kW heating28 kW cooling6,546 kWh/yr2.5$2,095
Mitsubishi Heavy Industries FDC280KXZPE128 kW heating28 kW cooling6,553 kWh/yr2.5$2,097
Toshiba MMY-MUP1001FT8P-A28 kW heating28 kW cooling6,104 kWh/yr4$1,953
Panasonic U-10LZ2E828 kW heating28 kW cooling5,879 kWh/yr2.5$1,881
Daikin REYA10AYM31.5 kW heating28 kW cooling6,052 kWh/yr3$1,937

Compare PUHY-P250YNW-A1-BS with another model

Mitsubishi Electric PUHY-P250YNW-A1-BS specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
28.00 kW
Cooling power input
7.18 kW
Rated heating capacity (7 Β°C)
31.50 kW
Heating power input
7.53 kW
EER, full load (tested)
3.91
COP, full load (tested)
4.46
Rated AEER
3.79
Rated ACOP
4.07
Standby power (PIA)
63.5 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
73.4 dB(A)
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-P250YNW-A1-BS zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,0126,628
Coldresidential2.50.01,64724,626
Mixedcommercial––3,9733,265
Mixedresidential2.50.02,5169,366
Hotcommercial––8,931595
Hotresidential3.51.56,983961
Part-load test points (18 values)
h__h2_ext_cap_power_rated
6090 W
c__t1_half_cap_power_rated
2920 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
3510 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
12400 W
h__h1_half_cap_heat_cap_rated
15750 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
2290 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
14000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
14000 W

Other model numbers on registration AAC9258

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9258
GEMS registration id
171852
Status
approved, available (self-reported)
Registration expires
20 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-P250YNW-A1 Series
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 20

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.