c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
26,058 kWh
5,230 cooling + 20,828 heating
Estimated running cost
$8,339 / year
$695 / month Β· $83,386 over 10 years
Capacity
56 kW cooling
63 kW heating

91% more electricity than the median of 41 comparable 50 kW reverse cycle registrations (13,613 kWh a year) in the mixed zone. Uses less than 5% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-P500YNW-A1 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 56,477$18,073$180,726
Mixed zone 26,058$8,339$83,386
Hot zone 17,069$5,462$54,621

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 56 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling5,421 kWh/yr2.5$1,735
Toshiba MMY-MUP2201FT8P-A61.5 kW heating61.5 kW cooling5,429 kWh/yr3$1,737
Mitsubishi Electric PUHY-M450YXM-A-BS50 kW heating50 kW cooling6,542 kWh/yr1.5$2,093
Mitsubishi Electric PUHY-M450YXM-A50 kW heating50 kW cooling6,542 kWh/yr1.5$2,093
Hitachi RAS-180RNCCLW56 kW heating50.4 kW cooling11,937 kWh/yr2.5$3,820

Air conditioners similar to the Mitsubishi Electric PUHY-P500YNW-A1

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP2001FT8P-A56 kW heating56 kW cooling16,337 kWh/yr3$5,228
Toshiba MMY-MUP20S1HT8P-A63 kW heating56 kW cooling5,421 kWh/yr2.5$1,735
Hitachi RAS-200RNCCLW63 kW heating56 kW cooling15,079 kWh/yr2.5$4,825
Daikin REYQ20TAY163 kW heating56 kW cooling19,870 kWh/yr2$6,358
Mitsubishi Heavy Industries FDC560KXZE263 kW heating56 kW cooling16,171 kWh/yr2.5$5,175
Hitachi RAS-200RNCBLW63 kW heating56 kW cooling13,993 kWh/yr2$4,478
Daikin REYA20AYM63 kW heating56 kW cooling13,423 kWh/yr3$4,295

Other Mitsubishi Electric models of similar capacity

ModelStarsEst. cost / yrCompare
Mitsubishi Electric PUHY-M500YXM-A-BS56 kW heating56 kW cooling8,090 kWh/yr1$2,589

Compare PUHY-P500YNW-A1 with another model

Mitsubishi Electric PUHY-P500YNW-A1 specifications

Type
Reverse cycle
Configuration
–
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
56.00 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
63.00 kW
Heating power input
–
EER, full load (tested)
3.55
COP, full load (tested)
4.02
Rated AEER
3.49
Rated ACOP
3.84
Standby power (PIA)
84.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-P500YNW-A1 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,47514,300
Coldresidential2.50.03,37353,104
Mixedcommercial––8,5077,055
Mixedresidential2.50.05,23020,828
Hotcommercial––19,3201,250
Hotresidential3.01.014,9292,140
Part-load test points (18 values)
h__h2_ext_cap_power_rated
10210 W
c__t1_half_cap_power_rated
6060 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
7590 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
23200 W
h__h1_half_cap_heat_cap_rated
31500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
4850 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
28000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
28000 W

Other model numbers on registration AAC9283

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9283
GEMS registration id
–
Status
approved
Registration expires
24 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-P500YNW-A1 Series
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.