Australia Β· costs in AUD
Reverse cycle multi-split / vrf air conditioner
Mitsubishi Heavy Industries FDC475KXZE2 Air Conditioner
Mitsubishi Heavy Industries FDC475KXZE2 is a 47.5 kW reverse cycle multi-split / vrf air conditioner registered under Australiaβs Energy Rating (GEMS) scheme (registration AAC10471).
- Energy rating (cooling)
- 2.5
- Heating: 1.5
- Annual electricity use
- 13,613 kWh
- 4,821 cooling + 8,792 heating
- Estimated running cost
- $4,356 / year
- $363 / month Β· $43,562 over 10 years
- Capacity
- 47.5 kW cooling
- 53 kW heating
1% less electricity than the median of 42 comparable 50 kW reverse cycle multi-split / vrf registrations (13,803 kWh a year) in the mixed zone. Uses less than 50% of them.
Across all 3,680 air conditioner registrations sold in Australia, it uses less than 5% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ 32c/kWh in AUD; change the price above to your tariff.
Mitsubishi Heavy Industries FDC475KXZE2 running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 28,143 | $9,006 | $90,058 |
| Mixed zone | 13,613 | $4,356 | $43,562 |
| Hot zone | 15,188 | $4,860 | $48,602 |
At 32c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Air conditioners that use less electricity
Same configuration and type, cooling capacity within 12% of 47.5 kW, at least 3% lower annual kWh in the mixed zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr | 2.5 | $1,300 | |
| Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr | 2.5 | $1,422 | |
| Toshiba MMY-MUP18S1HT8P-A54 kW heating50.4 kW cooling5,465 kWh/yr | 2 | $1,749 | |
| Mitsubishi Electric PUHY-M400YXM-A-BS45 kW heating45 kW cooling5,655 kWh/yr | 1.5 | $1,810 | |
| Mitsubishi Electric PUHY-M400YXM series45 kW heating45 kW cooling5,655 kWh/yr | 1.5 | $1,810 |
Air conditioners similar to the Mitsubishi Heavy Industries FDC475KXZE2
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Daikin REYA16AYM50 kW heating45 kW cooling11,471 kWh/yr | 3 | $3,671 | |
| Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr | 2.5 | $1,422 | |
| Hitachi RAS-160RNCCLW50 kW heating45 kW cooling11,174 kWh/yr | 2.5 | $3,576 | |
| Mitsubishi Electric PUHY-M400YXM-A45 kW heating45 kW cooling5,655 kWh/yr | 1.5 | $1,810 | |
| Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr | 2.5 | $1,300 | |
| Mitsubishi Electric PUHY-M400YXM-A-BS45 kW heating45 kW cooling5,655 kWh/yr | 1.5 | $1,810 | |
| Hitachi RAS-160RNCBLW47.5 kW heating45 kW cooling11,647 kWh/yr | 2 | $3,727 |
Other Mitsubishi Heavy Industries models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Mitsubishi Heavy Industries FDC475KXZRE247.5 kW heating47.5 kW cooling12,784 kWh/yr | 2 | $4,091 |
Compare FDC475KXZE2 with another model
Mitsubishi Heavy Industries FDC475KXZE2 specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 47.50 kW
- Cooling power input
- 14.57 kW
- Rated heating capacity (7 Β°C)
- 53.00 kW
- Heating power input
- 13.59 kW
- EER, full load (tested)
- 3.32
- COP, full load (tested)
- 3.66
- Rated AEER
- 3.23
- Rated ACOP
- 3.86
- Standby power (PIA)
- 45.7 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- Thailand
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Mitsubishi Heavy Industries FDC475KXZE2 zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 6,716 | 7,653 |
| Coldresidential | residential | 2.5 | 1.0 | 3,081 | 25,062 |
| Mixedcommercial | commercial | β | β | 8,458 | 3,625 |
| Mixedresidential | residential | 2.5 | 1.5 | 4,821 | 8,792 |
| Hotcommercial | commercial | β | β | 18,815 | 737 |
| Hotresidential | residential | 2.5 | 2.5 | 14,045 | 1,143 |
Part-load test points (16 values)
- h__h2_ext_cap_power_rated
- 15400 W
- c__t1_half_cap_power_rated
- 5350 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 5400 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 36500 W
- h__h1_half_cap_heat_cap_rated
- 25200 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 23800 W
- c__low_temp_have_half_cap_results
- No
Australian GEMS registration details
- Registration number
- AAC10471
- GEMS registration id
- 182047
- Status
- approved, available (self-reported)
- Registration expires
- 10 November 2031
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 21
Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 26 September 2026; last checked 27 September 2026. Manufacturer: mhiaa.com.au. How the derived figures are calculated.