Australia Β· costs in AUD

Reverse cycle packaged air conditioner
Temperzone OPA560RLTFPQ Air Conditioner
Temperzone OPA560RLTFPQ is a 53.5 kW reverse cycle ducted packaged air conditioner registered under Australiaβs Energy Rating (GEMS) scheme (registration AAC6437).
- Energy rating (cooling)
- 2
- Heating: 1
- Annual electricity use
- 17,223 kWh
- 6,066 cooling + 11,157 heating
- Estimated running cost
- $5,511 / year
- $459 / month Β· $55,114 over 10 years
- Capacity
- 53.5 kW cooling
- 57 kW heating
105% more electricity than the median of 24 comparable 50 kW reverse cycle ducted packaged registrations (8,422 kWh a year) in the mixed zone. Uses less than 13% of them.
Across all 3,680 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ 32c/kWh in AUD; change the price above to your tariff.
Temperzone OPA560RLTFPQ running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 32,956 | $10,546 | $105,459 |
| Mixed zone | 17,223 | $5,511 | $55,114 |
| Hot zone | 19,831 | $6,346 | $63,459 |
At 32c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Air conditioners that use less electricity
Same configuration and type, cooling capacity within 12% of 53.5 kW, at least 3% lower annual kWh in the mixed zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Caa HPA055R3AD53.3 kW heating53.4 kW cooling6,369 kWh/yr | 2 | $2,038 | |
| Actron Air PKY500T51.8 kW heating49.1 kW cooling6,700 kWh/yr | 1 | $2,144 | |
| APAC P055AHR3SA-LRR54 kW heating56.1 kW cooling6,902 kWh/yr | 1.5 | $2,209 | |
| APAC P055AHR3SA-LTT54 kW heating56.1 kW cooling6,902 kWh/yr | 1.5 | $2,209 | |
| Coates RPA-C05052.8 kW heating51.6 kW cooling7,171 kWh/yr | 1.5 | $2,295 |
Air conditioners similar to the Temperzone OPA560RLTFPQ
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Caa HPA055R3AD53.3 kW heating53.4 kW cooling6,369 kWh/yr | 2 | $2,038 | |
| Daikin UAYN530BFY1A54.3 kW heating53.4 kW cooling22,961 kWh/yr | 1 | $7,348 | |
| Daikin UAYN530AFY1A54.3 kW heating53.4 kW cooling22,961 kWh/yr | 1 | $7,348 | |
| Coates RPA-C05052.8 kW heating51.6 kW cooling7,171 kWh/yr | 1.5 | $2,295 | |
| Aggreko RPA-050D-R410A52.8 kW heating51.6 kW cooling7,171 kWh/yr | 1.5 | $2,295 | |
| AIRSTAGE RAQ/K/EC/WP/ECO/12050.2 kW heating51.2 kW cooling13,522 kWh/yr | 2 | $4,327 |
Other Temperzone models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OPA550RKTBG-P53.4 kW heating52.9 kW cooling7,577 kWh/yr | 1 | $2,425 | |
| Temperzone OPA 551RLTBP48.7 kW heating54.7 kW cooling16,837 kWh/yr | 1.5 | $5,388 |
Compare OPA560RLTFPQ with another model
Temperzone OPA560RLTFPQ specifications
- Type
- Reverse cycle
- Configuration
- Packaged
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 53.55 kW
- Cooling power input
- 17.90 kW
- Rated heating capacity (7 Β°C)
- 56.96 kW
- Heating power input
- 19.10 kW
- EER, full load (tested)
- 2.99
- COP, full load (tested)
- 2.98
- Rated AEER
- 2.99
- Rated ACOP
- 2.98
- Standby power (PIA)
- 11.5 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R32
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- New Zealand, Australia
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Temperzone OPA560RLTFPQ zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 7,476 | 9,477 |
| Coldresidential | residential | 2.0 | 1.0 | 3,918 | 29,038 |
| Mixedcommercial | commercial | β | β | 10,005 | 5,057 |
| Mixedresidential | residential | 2.0 | 1.0 | 6,066 | 11,157 |
| Hotcommercial | commercial | β | β | 23,858 | 1,040 |
| Hotresidential | residential | 2.0 | 1.0 | 18,183 | 1,648 |
Part-load test points (21 values)
- c__t1_min_cap_power_rated
- 6080 W
- c__t1_half_cap_power_rated
- 8220 W
- c__t1_have_min_cap_results
- Yes
- h__h1_half_cap_power_rated
- 8690 W
- h__h1_have_min_cap_results
- No
- h__h2_full_cap_power_rated
- 16774 W
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h1_half_cap_heat_cap_rated
- 27650 W
- h__h2_full_cap_heat_cap_rated
- 42873 W
- h__h2_is_capable_extended_load
- No
- c__low_temp_min_cap_power_rated
- 4590 W
- c__t1_min_cap_cooling_cap_rated
- 17350 W
- c__low_temp_full_cap_power_rated
- 16360.6 W
- c__low_temp_half_cap_power_rated
- 6880 W
- c__t1_half_cap_cooling_cap_rated
- 27740 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_min_cap_cooling_cap_rated
- 18170 W
- c__low_temp_full_cap_cooling_cap_rated
- 57673.35 W
- c__low_temp_half_cap_cooling_cap_rated
- 28040 W
Australian GEMS registration details
- Registration number
- AAC6437
- GEMS registration id
- 137392
- Status
- approved, available (self-reported)
- Registration expires
- 13 February 2027
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- β
- Regulatory standard
- [SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2019
- Product class
- Class 7
Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.