c/kWh
Energy rating (cooling)
2
Heating: 1.5
Annual electricity use
15,167 kWh
2,273 cooling + 12,894 heating
Estimated running cost
$5,005 / year
$417 / month Β· $50,051 over 10 years
Capacity
29.6 kW cooling
29.8 kW heating

8% more electricity than the median of 17 comparable 25 kW reverse cycle ducted packaged registrations (14,025 kWh a year) in the cold zone. Uses less than 18% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 9% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Actron Air PKV290T-T running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 15,167$5,005$50,051
Mixed zone 8,476$2,797$27,971
Hot zone 11,083$3,657$36,574

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 29.6 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P029AHR3SA-LRR30.1 kW heating31 kW cooling2,267 kWh/yr2$748
APAC P029AHR3SA-30.1 kW heating31 kW cooling2,267 kWh/yr2$748
Caa VPA030R3AC33.1 kW heating32.1 kW cooling2,638 kWh/yr1.5$871
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling2,665 kWh/yr1.5$879
Actron Air PCG330U33 kW heating32 kW cooling2,779 kWh/yr1.5$917

Heat pumps similar to the Actron Air PKV290T-T

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAYN300AFY1A28.6 kW heating29.6 kW cooling37,764 kWh/yr0$12,462
Temperzone OPA294RKTB27.2 kW heating28.3 kW cooling15,012 kWh/yr1.5$4,954
APAC P029AHR3SA-LTT30.1 kW heating31 kW cooling2,267 kWh/yr2$748
APAC P029AHR3SA-LBB30.1 kW heating31 kW cooling2,267 kWh/yr2$748
Temperzone OPA 281RLTP25.3 kW heating28.2 kW cooling14,130 kWh/yr1.5$4,663
AIRSTAGE RAQ/K/WP/ECO/11232.1 kW heating31.7 kW cooling18,409 kWh/yr1.5$6,075

Other Actron Air models of similar capacity

ModelStarsEst. cost / yrCompare
Actron Air PKV290T-L30.2 kW heating29.5 kW cooling15,572 kWh/yr1.5$5,139
Actron Air PKV290T-L/R30.2 kW heating29.5 kW cooling15,572 kWh/yr1.5$5,139

Compare PKV290T-T with another model

Actron Air PKV290T-T specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
29.60 kW
Cooling power input
8.63 kW
Rated heating capacity (7 Β°C)
29.80 kW
Heating power input
7.91 kW
EER, full load (tested)
3.36
COP, full load (tested)
3.68
Rated AEER
3.42
Rated ACOP
3.76
Standby power (PIA)
7.0 W
Compressor
Variable speed, Digital Scroll
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes (mode 1 on off, mode 2 50 percent, mode 3 75 percent)
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Actron Air PKV290T-T zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––5,3184,351
Coldresidential2.01.52,27312,894
Mixedcommercial––6,5812,349
Mixedresidential2.01.53,4715,005
Hotcommercial––14,148499
Hotresidential2.01.510,299784
Part-load test points (18 values)
c__t1_half_cap_power_rated
4463 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
4096 W
h__h1_have_min_cap_results
No
h__h2_full_cap_power_rated
6860 W
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_half_cap_heat_cap_rated
14220 W
h__h2_full_cap_heat_cap_rated
23435 W
h__h2_is_capable_extended_load
No
c__low_temp_full_cap_power_rated
7885.61726 W
c__low_temp_half_cap_power_rated
4079.1820000000002 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
14394 W
c__low_temp_have_half_cap_results
No
c__low_temp_full_cap_cooling_cap_rated
31879.199999999997 W
c__low_temp_half_cap_cooling_cap_rated
15502.338 W

New Zealand E3 registration details

Registration number
AAC8050
GEMS registration id
158876
Status
approved, available (self-reported)
Registration expires
7 February 2029
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: actronair.com.au. How the derived figures are calculated.