c/kWh
Energy rating (cooling)
1.5
Heating: 0
Annual electricity use
100,535 kWh
8,833 cooling + 91,702 heating
Estimated running cost
$33,177 / year
$2,765 / month Β· $331,766 over 10 years
Capacity
100 kW cooling
95 kW heating

142% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 8% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Aggreko RPA-100D-R410A running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 100,535$33,177$331,766
Mixed zone 49,910$16,470$164,703
Hot zone 43,890$14,484$144,837

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 100 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Temperzone OPA970RLTB1FPQ88.2 kW heating88.9 kW cooling8,214 kWh/yr1.5$2,711
Temperzone OPA960RKTBG-P88.9 kW heating92 kW cooling8,576 kWh/yr1$2,830
APAC P095AHR3SA-LXX92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
APAC P095AHR3SA-RXX92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
Caa HPC115R3AD121.7 kW heating111.2 kW cooling9,750 kWh/yr1.5$3,218

Heat pumps similar to the Aggreko RPA-100D-R410A

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Coates RPA-C10095 kW heating100 kW cooling64,633 kWh/yr1.5$21,329
Caa HPC100R3AD101.3 kW heating97.2 kW cooling21,754 kWh/yr1.5$7,179
Actron Air PRV96AT97 kW heating96 kW cooling50,459 kWh/yr2.5$16,651
Daikin UAYN940AFY1A94 kW heating94.9 kW cooling56,405 kWh/yr1$18,614
APAC P095AHR3SA-RXX92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
APAC P095AHR3SA-LTT92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
Temperzone OPA960RKTBG-P88.9 kW heating92 kW cooling8,576 kWh/yr1$2,830
Temperzone OPA 970RLTB2FPQD95.8 kW heating91 kW cooling52,473 kWh/yr2$17,316

Compare RPA-100D-R410A with another model

Aggreko RPA-100D-R410A specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
100.00 kW
Cooling power input
32.50 kW
Rated heating capacity (7 Β°C)
95.00 kW
Heating power input
31.14 kW
EER, full load (tested)
2.99
COP, full load (tested)
2.96
Rated AEER
3.08
Rated ACOP
3.05
Standby power (PIA)
1.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Aggreko RPA-100D-R410A zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––20,67125,299
Coldresidential1.50.08,83391,702
Mixedcommercial––25,53412,324
Mixedresidential1.50.013,42436,486
Hotcommercial––55,4072,049
Hotresidential1.50.540,1623,728
Part-load test points (4 values)
h__h2_full_cap_power_rated
26980 W
h__h3_have_full_cap_results
No
h__h2_full_cap_heat_cap_rated
63500 W
c__low_temp_have_full_cap_results
No

New Zealand E3 registration details

Registration number
AAC7969
GEMS registration id
158496
Status
approved, available (self-reported)
Registration expires
16 December 2028
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. Manufacturer: coldmagic.com.cn. How the derived figures are calculated.