c/kWh
Energy rating (cooling)
1
Heating: 0
Annual electricity use
8,576 kWh
Estimated running cost
$2,830 / year
$236 / month Β· $28,301 over 10 years
Capacity
92 kW cooling
88.9 kW heating

79% less electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 89% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 16% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Temperzone OPA960RKTBG-P running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 8,576$2,830$28,301
Mixed zone 13,013$4,294$42,943
Hot zone 38,775$12,796$127,958

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 92 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Temperzone OPA855RKTBG-P77.6 kW heating81.4 kW cooling7,082 kWh/yr1.5$2,337
APAC P085AHR3SA-LTR80.8 kW heating84.1 kW cooling7,214 kWh/yr1.5$2,381
APAC P085AHR3SA-LTT80.8 kW heating84.1 kW cooling7,214 kWh/yr1.5$2,381
Temperzone OPA970RLTB1FPQ88.2 kW heating88.9 kW cooling8,214 kWh/yr1.5$2,711

Heat pumps similar to the Temperzone OPA960RKTBG-P

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/K/EC/WP/ECO/23692.6 kW heating90.4 kW cooling52,477 kWh/yr1.5$17,317
AIRSTAGE RAQ/K/EC/WP/*23692.6 kW heating90.4 kW cooling52,477 kWh/yr1.5$17,317
APAC P095AHR3SA-92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
APAC P095AHR3SA-RXX92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
Daikin UAYN940AFY1A94 kW heating94.9 kW cooling56,405 kWh/yr1$18,614
Actron Air PRV96AT97 kW heating96 kW cooling50,459 kWh/yr2.5$16,651

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone FPA 970RLTB2FPQD95.8 kW heating91 kW cooling52,473 kWh/yr2$17,316
Temperzone OPA970RLTB2FPQ95.8 kW heating91 kW cooling52,473 kWh/yr2$17,316

Compare OPA960RKTBG-P with another model

Temperzone OPA960RKTBG-P specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
91.95 kW
Cooling power input
31.32 kW
Rated heating capacity (7 Β°C)
88.86 kW
Heating power input
24.30 kW
EER, full load (tested)
2.94
COP, full load (tested)
3.66
Rated AEER
2.93
Rated ACOP
3.65
Standby power (PIA)
20.0 W
Compressor
Variable speed, Digital Scroll
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA960RKTBG-P zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––19,980–
Coldresidential1.00.08,576–
Mixedcommercial––24,667–
Mixedresidential1.00.013,013–
Hotcommercial––53,453–
Hotresidential1.50.038,775–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

New Zealand E3 registration details

Registration number
AAC7152
GEMS registration id
150371
Status
approved, available (self-reported)
Registration expires
14 November 2027
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
Simulation
MEPS
2020
Product class
Class 24

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.