New Zealand Β· costs in NZD

Reverse cycle packaged air conditioner
Temperzone OPA970RLTB2FPQ Heat Pump
Temperzone OPA970RLTB2FPQ is a 91 kW reverse cycle ducted packaged heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC7080).
- Energy rating (cooling)
- 2
- Heating: 1
- Annual electricity use
- 52,473 kWh
- 6,895 cooling + 45,578 heating
- Estimated running cost
- $17,316 / year
- $1,443 / month Β· $173,161 over 10 years
- Capacity
- 91 kW cooling
- 95.8 kW heating
26% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 36% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Temperzone OPA970RLTB2FPQ running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 52,473 | $17,316 | $173,161 |
| Mixed zone | 28,734 | $9,482 | $94,822 |
| Hot zone | 34,532 | $11,396 | $113,956 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 91 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OPA855RKTBG-P77.6 kW heating81.4 kW cooling7,082 kWh/yr | 1.5 | $2,337 | |
| APAC P085AHR3SA-RRR80.8 kW heating84.1 kW cooling7,214 kWh/yr | 1.5 | $2,381 | |
| APAC P085AHR3SA-RTR80.8 kW heating84.1 kW cooling7,214 kWh/yr | 1.5 | $2,381 | |
| Temperzone OPA970RLTB1FPQ88.2 kW heating88.9 kW cooling8,214 kWh/yr | 1.5 | $2,711 | |
| Caa HPC100R3AD101.3 kW heating97.2 kW cooling21,754 kWh/yr | 1.5 | $7,179 |
Heat pumps similar to the Temperzone OPA970RLTB2FPQ
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| AIRSTAGE RAQ/K/EC/WP/*23692.6 kW heating90.4 kW cooling52,477 kWh/yr | 1.5 | $17,317 | |
| AIRSTAGE RAQ/K/EC/WP/23692.6 kW heating90.4 kW cooling52,477 kWh/yr | 1.5 | $17,317 | |
| APAC P095AHR3SA-92.2 kW heating94.1 kW cooling8,763 kWh/yr | 1 | $2,892 | |
| APAC P095AHR3SA-RTT92.2 kW heating94.1 kW cooling8,763 kWh/yr | 1 | $2,892 | |
| Daikin UAYN940AFY1A94 kW heating94.9 kW cooling56,405 kWh/yr | 1 | $18,614 | |
| Actron Air PRV96AT97 kW heating96 kW cooling50,459 kWh/yr | 2.5 | $16,651 |
Other Temperzone models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OPA960RKTBG-P88.9 kW heating92 kW cooling8,576 kWh/yr | 1 | $2,830 | |
| Temperzone OPA970RLTB1FPQ88.2 kW heating88.9 kW cooling8,214 kWh/yr | 1.5 | $2,711 |
Compare OPA970RLTB2FPQ with another model
Temperzone OPA970RLTB2FPQ specifications
- Type
- Reverse cycle
- Configuration
- Packaged
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 91.00 kW
- Cooling power input
- 29.89 kW
- Rated heating capacity (7 Β°C)
- 95.83 kW
- Heating power input
- 28.68 kW
- EER, full load (tested)
- 2.99
- COP, full load (tested)
- 3.34
- Rated AEER
- 3.04
- Rated ACOP
- 3.33
- Standby power (PIA)
- 23.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R32
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- Australia, New Zealand
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Temperzone OPA970RLTB2FPQ zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 14,641 | 15,893 |
| Coldresidential | residential | 2.0 | 1.0 | 6,895 | 45,578 |
| Mixedcommercial | commercial | β | β | 18,902 | 8,893 |
| Mixedresidential | residential | 2.0 | 1.0 | 10,678 | 18,056 |
| Hotcommercial | commercial | β | β | 42,262 | 1,885 |
| Hotresidential | residential | 2.0 | 1.0 | 31,662 | 2,870 |
Part-load test points (25 values)
- c__t1_min_cap_power_rated
- 9979 W
- h__h1_min_cap_power_rated
- 8784 W
- h__h2_ext_cap_power_rated
- 32102 W
- c__t1_half_cap_power_rated
- 13619 W
- c__t1_have_min_cap_results
- Yes
- h__h1_half_cap_power_rated
- 14801 W
- h__h1_have_min_cap_results
- Yes
- h__h2_full_cap_power_rated
- 27091 W
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- Yes
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h1_min_cap_heat_cap_rated
- 22180 W
- h__h2_ext_cap_heat_cap_rated
- 84908 W
- h__h1_half_cap_heat_cap_rated
- 50050 W
- h__h2_full_cap_heat_cap_rated
- 75789 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_min_cap_power_rated
- 8157 W
- c__t1_min_cap_cooling_cap_rated
- 28060 W
- c__low_temp_half_cap_power_rated
- 11701 W
- c__t1_half_cap_cooling_cap_rated
- 45380 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_min_cap_cooling_cap_rated
- 28860 W
- c__low_temp_half_cap_cooling_cap_rated
- 47270 W
Other model numbers on registration AAC7080
Registered together and sharing the same test results. Usually variants of the same unit.
New Zealand E3 registration details
- Registration number
- AAC7080
- GEMS registration id
- 141172
- Status
- approved, available (self-reported)
- Registration expires
- 9 October 2027
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- OPA 970RLTB2FPQD
- Regulatory standard
- [SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2020
- Product class
- Class 24
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.