c/kWh
Energy rating (cooling)
1.5
Heating: 1.5
Annual electricity use
43,255 kWh
6,661 cooling + 36,594 heating
Estimated running cost
$14,274 / year
$1,190 / month Β· $142,742 over 10 years
Capacity
83.1 kW cooling
84.1 kW heating

4% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 45% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 2% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

AIRSTAGE RAQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 43,255$14,274$142,742
Mixed zone 24,608$8,121$81,206
Hot zone 32,275$10,651$106,508

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 83.1 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P075AHR3SA-RBB72.9 kW heating75.5 kW cooling6,399 kWh/yr1.5$2,112
APAC P075AHR3SA-RRR72.9 kW heating75.5 kW cooling6,399 kWh/yr1.5$2,112
Temperzone OPA 820RLTB1FPQ79 kW heating78.4 kW cooling6,702 kWh/yr1.5$2,212
Temperzone OPA855RKTBG-P77.6 kW heating81.4 kW cooling7,082 kWh/yr1.5$2,337
AIRSTAGE RAQ/L/EC/WP/23480.5 kW heating83.7 kW cooling40,796 kWh/yr2$13,463

Heat pumps similar to the AIRSTAGE RAQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
APAC P085AHR3SA-80.8 kW heating84.1 kW cooling7,214 kWh/yr1.5$2,381
APAC P085AHR3SA-LBB80.8 kW heating84.1 kW cooling7,214 kWh/yr1.5$2,381
Daikin UAYN840AFY1A82 kW heating81.9 kW cooling49,366 kWh/yr1$16,291
Temperzone OPA855RKTBG-P77.6 kW heating81.4 kW cooling7,082 kWh/yr1.5$2,337
Actron Air PRV85AT86 kW heating85 kW cooling41,538 kWh/yr2.5$13,708
Temperzone OPA 820RLTB2FPQD81.4 kW heating80.2 kW cooling43,532 kWh/yr2.5$14,366

Other AIRSTAGE models of similar capacity

ModelStarsEst. cost / yrCompare
AIRSTAGE RAQ/L/EC/WP/23480.5 kW heating83.7 kW cooling40,796 kWh/yr2$13,463
AIRSTAGE RAQ/L/EC/WP/23687 kW heating89.1 kW cooling47,487 kWh/yr1.5$15,671

Compare RAQ/K/EC/WP/234 with another model

AIRSTAGE RAQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
83.09 kW
Cooling power input
24.15 kW
Rated heating capacity (7 Β°C)
84.09 kW
Heating power input
22.81 kW
EER, full load (tested)
3.25
COP, full load (tested)
3.59
Rated AEER
3.43
Rated ACOP
3.67
Standby power (PIA)
30.0 W
Compressor
Variable speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

AIRSTAGE RAQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––15,45112,398
Coldresidential1.51.56,66136,594
Mixedcommercial––19,0656,732
Mixedresidential1.51.510,09114,517
Hotcommercial––41,2611,459
Hotresidential2.01.529,9532,322
Part-load test points (4 values)
h__h2_full_cap_power_rated
21680 W
h__h3_have_full_cap_results
No
h__h2_full_cap_heat_cap_rated
74370 W
c__low_temp_have_full_cap_results
No

Other model numbers on registration AAC9263

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC9263
GEMS registration id
172164
Status
approved, available (self-reported)
Registration expires
20 August 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
RAQ/K/EC/WP/234
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: fujitsugeneral.com.au. How the derived figures are calculated.