New Zealand Β· costs in NZD

Reverse cycle packaged air conditioner
AIRSTAGE URT/EC/WP/MS 101 S/K Heat Pump
AIRSTAGE URT/EC/WP/MS 101 S/K is a 109.7 kW reverse cycle ducted packaged heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC9573).
A newer registration of this model exists: AAC9573.
- Energy rating (cooling)
- 1
- Heating: 1.5
- Annual electricity use
- 59,964 kWh
- 10,316 cooling + 49,648 heating
- Estimated running cost
- $19,788 / year
- $1,649 / month Β· $197,881 over 10 years
- Capacity
- 109.7 kW cooling
- 115.8 kW heating
44% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 28% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
AIRSTAGE URT running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 59,964 | $19,788 | $197,881 |
| Mixed zone | 35,292 | $11,646 | $116,464 |
| Hot zone | 49,666 | $16,390 | $163,898 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 109.7 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Caa HPC115R3AD121.7 kW heating111.2 kW cooling9,750 kWh/yr | 1.5 | $3,218 | |
| APAC P115AHR3SA-CRR109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| APAC P115AHR3SA-109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| Caa HPC100R3AD101.3 kW heating97.2 kW cooling21,754 kWh/yr | 1.5 | $7,179 |
Heat pumps similar to the AIRSTAGE URT
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Caa HPC115R3AD121.7 kW heating111.2 kW cooling9,750 kWh/yr | 1.5 | $3,218 | |
| APAC P115AHR3SA-CBR109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| APAC P115AHR3SA-CRR109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| Aggreko RPA-100D-R410A95 kW heating100 kW cooling100,535 kWh/yr | 1.5 | $33,177 | |
| Coates RPA-C10095 kW heating100 kW cooling64,633 kWh/yr | 1.5 | $21,329 | |
| Caa HPC100R3AD101.3 kW heating97.2 kW cooling21,754 kWh/yr | 1.5 | $7,179 |
Other AIRSTAGE models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| AIRSTAGE RAQ/K/EC/WP/238118.8 kW heating115.6 kW cooling68,734 kWh/yr | 1.5 | $22,682 | |
| AIRSTAGE RAQ/K/EC/WP/ECO/238118.8 kW heating115.6 kW cooling68,734 kWh/yr | 1.5 | $22,682 |
Compare URT/EC/WP/MS 101 S/K with another model
AIRSTAGE URT specifications
- Type
- Reverse cycle
- Configuration
- Packaged
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 109.70 kW
- Cooling power input
- 37.60 kW
- Rated heating capacity (7 Β°C)
- 115.80 kW
- Heating power input
- 30.55 kW
- EER, full load (tested)
- 2.97
- COP, full load (tested)
- 3.81
- Rated AEER
- 2.91
- Rated ACOP
- 3.78
- Standby power (PIA)
- 30.0 W
- Compressor
- Variable speed
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- Italy
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
AIRSTAGE URT zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 24,005 | 16,721 |
| Coldresidential | residential | 1.0 | 1.5 | 10,316 | 49,648 |
| Mixedcommercial | commercial | β | β | 29,631 | 9,040 |
| Mixedresidential | residential | 1.0 | 1.5 | 15,645 | 19,647 |
| Hotcommercial | commercial | β | β | 64,189 | 1,935 |
| Hotresidential | residential | 1.5 | 1.5 | 46,572 | 3,094 |
Part-load test points (4 values)
- h__h2_full_cap_power_rated
- 29820 W
- h__h3_have_full_cap_results
- No
- h__h2_full_cap_heat_cap_rated
- 102800 W
- c__low_temp_have_full_cap_results
- No
Other model numbers on registration AAC9573
Registered together and sharing the same test results. Usually variants of the same unit.
New Zealand E3 registration details
- Registration number
- AAC9573
- GEMS registration id
- 174269
- Status
- approved, available (self-reported)
- Registration expires
- 19 November 2030
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- URT/EC/WP/MS/101/SK
- Regulatory standard
- [SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2020
- Product class
- Class 24
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: fujitsugeneral.com.au. How the derived figures are calculated.