c/kWh
Energy rating (cooling)
1.5
Heating: 0
Annual electricity use
2,853 kWh
Estimated running cost
$941 / year
$78 / month Β· $9,415 over 10 years
Capacity
34.7 kW cooling
37.4 kW heating

9% less electricity than the median of 30 comparable 35 kW reverse cycle ducted packaged registrations (3,122 kWh a year) in the cold zone. Uses less than 73% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 64% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Caa VPA035R3AC running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 2,853$941$9,415
Mixed zone 4,325$1,427$14,273
Hot zone 12,861$4,244$42,441

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 34.7 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P029AHR3SA-RBB30.1 kW heating31 kW cooling2,267 kWh/yr2$748
APAC P029AHR3SA-RTR30.1 kW heating31 kW cooling2,267 kWh/yr2$748
Caa VPA030R3AC33.1 kW heating32.1 kW cooling2,638 kWh/yr1.5$871
Temperzone OPA340RKTB30.7 kW heating32.1 kW cooling2,665 kWh/yr1.5$879

Heat pumps similar to the Caa VPA035R3AC

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Temperzone OPA350RLTFPQ37 kW heating34.8 kW cooling19,674 kWh/yr2.5$6,492
Daikin UAYQ120CY1A35.8 kW heating34.4 kW cooling20,327 kWh/yr1$6,708
APAC P033AHR3SA-RTR32.9 kW heating34.4 kW cooling2,462 kWh/yr2$812
APAC P033AHR3SA-LTT32.9 kW heating34.4 kW cooling2,462 kWh/yr2$812
AIRSTAGE RAQ/L/EC/WP/11229.6 kW heating33.9 kW cooling17,014 kWh/yr1.5$5,615
Actron Air PCA340U35.5 kW heating33.5 kW cooling3,084 kWh/yr1$1,018
AIRSTAGE RAQ/K/WP/11536.2 kW heating36.1 kW cooling20,730 kWh/yr1.5$6,841
Actron Air PCG340R34.7 kW heating33.1 kW cooling19,927 kWh/yr1.5$6,576

Compare VPA035R3AC with another model

Caa VPA035R3AC specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
34.73 kW
Cooling power input
10.38 kW
Rated heating capacity (7 Β°C)
37.40 kW
Heating power input
10.36 kW
EER, full load (tested)
3.19
COP, full load (tested)
3.60
Rated AEER
3.34
Rated ACOP
3.60
Standby power (PIA)
10.0 W
Compressor
Fixed speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Caa VPA035R3AC zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,631–
Coldresidential1.50.02,853–
Mixedcommercial––8,184–
Mixedresidential1.50.04,325–
Hotcommercial––17,722–
Hotresidential2.00.012,861–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

New Zealand E3 registration details

Registration number
AAC6934
GEMS registration id
149414
Status
approved, available (self-reported)
Registration expires
4 September 2027
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 6

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. How the derived figures are calculated.