c/kWh
Energy rating (cooling)
2
Heating: 1
Annual electricity use
13,126 kWh
1,542 cooling + 11,584 heating
Estimated running cost
$4,332 / year
$361 / month Β· $43,316 over 10 years
Capacity
22.4 kW cooling
25 kW heating

47% more electricity than the median of 18 comparable 20 kW reverse cycle ducted multi-split / vrf registrations (8,936 kWh a year) in the cold zone. Uses less than 0% of them.

Across all 3,612 air conditioner registrations sold in Australia, it uses less than 10% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Gree GMV-224WL running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 13,126$4,332$43,316
Mixed zone 6,534$2,156$21,562
Hot zone 7,436$2,454$24,539

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 22.4 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Panasonic U-8ME2R8E25 kW heating22.4 kW cooling6,860 kWh/yr3$2,264
Panasonic U-8ME2R825 kW heating22.4 kW cooling6,860 kWh/yr3$2,264
Gree GMV-224WM/C-X(A) / GMV-NDR22P/X1-T22.4 kW heating22.4 kW cooling8,151 kWh/yr2.5$2,690
Braemar MCHX224D313B22.4 kW heating22.4 kW cooling8,151 kWh/yr2.5$2,690
iCongo AU-V215W/N4-G0126.1 kW heating21.5 kW cooling8,311 kWh/yr4.5$2,743

Heat pumps similar to the Gree GMV-224WL

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Haier AV08IMAURA25 kW heating22.4 kW cooling12,201 kWh/yr2$4,026
Braemar MCRX224D313B22.4 kW heating22.4 kW cooling9,333 kWh/yr2$3,080
Samsung Electronics AM080FXMDGH/EU25 kW heating22.4 kW cooling11,192 kWh/yr1.5$3,693
Mitsubishi Heavy Industries FDC224KXZRE222.4 kW heating22.4 kW cooling10,745 kWh/yr2$3,546
Panasonic U-8ME2R8E25 kW heating22.4 kW cooling6,860 kWh/yr3$2,264
Mitsubishi Electric PUMY-P200YKMD2-A Series25 kW heating22.4 kW cooling12,287 kWh/yr2.5$4,055
Braemar MCHX224D313B22.4 kW heating22.4 kW cooling8,151 kWh/yr2.5$2,690
Panasonic U-8ME2R825 kW heating22.4 kW cooling6,860 kWh/yr3$2,264

Compare GMV-224WL/A-X(A) with another model

Gree GMV-224WL specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
22.40 kW
Cooling power input
7.17 kW
Rated heating capacity (7 Β°C)
25.00 kW
Heating power input
6.52 kW
EER, full load (tested)
3.03
COP, full load (tested)
3.74
Rated AEER
3.06
Rated ACOP
3.75
Standby power (PIA)
40.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
76.9 dB(A)
Demand response (AS/NZS 4755)
Yes
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Gree GMV-224WL zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,2743,600
Coldresidential2.01.01,54211,584
Mixedcommercial––4,1181,740
Mixedresidential2.01.52,3994,135
Hotcommercial––9,122387
Hotresidential2.52.56,849587
Part-load test points (16 values)
h__h2_ext_cap_power_rated
6944 W
c__t1_half_cap_power_rated
2544 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
2674 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
17500 W
h__h1_half_cap_heat_cap_rated
12500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
11200 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC9586
GEMS registration id
174551
Status
approved, available (self-reported)
Registration expires
30 November 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 20

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.