c/kWh
Energy rating (cooling)
2
Heating: 1
Annual electricity use
32,460 kWh
4,272 cooling + 28,188 heating
Estimated running cost
$10,712 / year
$893 / month Β· $107,118 over 10 years
Capacity
56 kW cooling
58 kW heating

34% more electricity than the median of 10 comparable 50 kW reverse cycle ducted multi-split / vrf registrations (24,311 kWh a year) in the cold zone. Uses less than 10% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Haier AV20IMAURA running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 32,460$10,712$107,118
Mixed zone 17,055$5,628$56,282
Hot zone 20,811$6,868$68,676

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 56 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Haier AV18IMAURA56.5 kW heating50 kW cooling3,682 kWh/yr2$1,215
Panasonic U-18ME2R8 / S-22MF2E5A / S-90MF2E5A / S-106MF2E5A56 kW heating50 kW cooling26,274 kWh/yr3.5$8,670
Panasonic U-18ME2R856 kW heating50 kW cooling26,274 kWh/yr3.5$8,670

Heat pumps similar to the Haier AV20IMAURA

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Panasonic U-20ME2R8E63 kW heating56 kW cooling34,255 kWh/yr3.5$11,304
Panasonic U-20ME2R863 kW heating56 kW cooling34,255 kWh/yr3.5$11,304

Other Haier models of similar capacity

ModelStarsEst. cost / yrCompare
Haier AV18IMAURA56.5 kW heating50 kW cooling3,682 kWh/yr2$1,215

Compare AV20IMAURA with another model

Haier AV20IMAURA specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
56.00 kW
Cooling power input
18.50 kW
Rated heating capacity (7 Β°C)
58.00 kW
Heating power input
16.70 kW
EER, full load (tested)
3.04
COP, full load (tested)
3.36
Rated AEER
3.00
Rated ACOP
3.44
Standby power (PIA)
50.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Haier AV20IMAURA zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––9,5408,646
Coldresidential2.01.04,27228,188
Mixedcommercial––11,9184,469
Mixedresidential2.01.56,60910,446
Hotcommercial––26,174927
Hotresidential2.02.019,3561,455
Part-load test points (14 values)
c__t1_half_cap_power_rated
7800 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
7200 W
h__h1_have_min_cap_results
No
h__h2_full_cap_power_rated
22500 W
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_half_cap_heat_cap_rated
29000 W
h__h2_full_cap_heat_cap_rated
45000 W
h__h2_is_capable_extended_load
No
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
28000 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC9278
GEMS registration id
172089
Status
approved, available (self-reported)
Registration expires
10 September 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. Manufacturer: haierhome.com.au. How the derived figures are calculated.