c/kWh
Energy rating (cooling)
3.5
Heating: 1
Annual electricity use
34,255 kWh
2,900 cooling + 31,355 heating
Estimated running cost
$11,304 / year
$942 / month Β· $113,042 over 10 years
Capacity
56 kW cooling
63 kW heating

41% more electricity than the median of 10 comparable 50 kW reverse cycle ducted multi-split / vrf registrations (24,311 kWh a year) in the cold zone. Uses less than 0% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Panasonic U-20ME2R8E running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 34,255$11,304$113,042
Mixed zone 15,403$5,083$50,830
Hot zone 14,876$4,909$49,091

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 56 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Haier AV18IMAURA56.5 kW heating50 kW cooling3,682 kWh/yr2$1,215
Panasonic U-18ME2R8 / S-22MF2E5A / S-90MF2E5A / S-106MF2E5A56 kW heating50 kW cooling26,274 kWh/yr3.5$8,670
Panasonic U-18ME2R856 kW heating50 kW cooling26,274 kWh/yr3.5$8,670
Haier AV20IMAURA58 kW heating56 kW cooling32,460 kWh/yr2$10,712

Heat pumps similar to the Panasonic U-20ME2R8E

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Haier AV20IMAURA58 kW heating56 kW cooling32,460 kWh/yr2$10,712
Haier AV18IMAURA56.5 kW heating50 kW cooling3,682 kWh/yr2$1,215

Other Panasonic models of similar capacity

ModelStarsEst. cost / yrCompare
Panasonic U-18ME2R8 / S-22MF2E5A / S-90MF2E5A / S-106MF2E5A56 kW heating50 kW cooling26,274 kWh/yr3.5$8,670
Panasonic U-18ME2R856 kW heating50 kW cooling26,274 kWh/yr3.5$8,670

Compare U-20ME2R8E with another model

Panasonic U-20ME2R8E specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
56.00 kW
Cooling power input
19.20 kW
Rated heating capacity (7 Β°C)
63.00 kW
Heating power input
17.50 kW
EER, full load (tested)
2.82
COP, full load (tested)
3.47
Rated AEER
2.87
Rated ACOP
3.54
Standby power (PIA)
83.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes (mode 1 on off, mode 2 50 percent, mode 3 75 percent)
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Panasonic U-20ME2R8E zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,2898,642
Coldresidential3.51.02,90031,355
Mixedcommercial––5,7664,161
Mixedresidential3.01.54,67510,728
Hotcommercial––16,672734
Hotresidential3.54.013,7081,168
Part-load test points (21 values)
c__t1_min_cap_power_rated
880 W
h__h1_min_cap_power_rated
740 W
h__h2_ext_cap_power_rated
14800 W
c__t1_half_cap_power_rated
4850 W
c__t1_have_min_cap_results
Yes
h__h1_half_cap_power_rated
5600 W
h__h1_have_min_cap_results
Yes
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_min_cap_heat_cap_rated
4280 W
h__h2_ext_cap_heat_cap_rated
38000 W
h__h1_half_cap_heat_cap_rated
31500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_min_cap_power_rated
590 W
c__t1_min_cap_cooling_cap_rated
6700 W
c__t1_half_cap_cooling_cap_rated
28000 W
c__low_temp_have_half_cap_results
No
c__low_temp_min_cap_cooling_cap_rated
6800 W

Other model numbers on registration AAC9307

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC9307
GEMS registration id
170372
Status
approved, available (self-reported)
Registration expires
24 September 2030
Registered for sale in
Australia, New Zealand
Family
U-20ME2R8
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.