c/kWh
Energy rating (cooling)
2.5
Heating: 1.5
Annual electricity use
13,265 kWh
1,566 cooling + 11,699 heating
Estimated running cost
$4,377 / year
$365 / month Β· $43,775 over 10 years
Capacity
23.5 kW cooling
28 kW heating

2% more electricity than the median of 15 comparable 25 kW reverse cycle ducted split system registrations (13,045 kWh a year) in the cold zone. Uses less than 40% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 10% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Mitsubishi Heavy Industries FDCA250VSA-W running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 13,265$4,377$43,775
Mixed zone 6,676$2,203$22,031
Hot zone 7,798$2,573$25,733

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 23.5 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Actron Air CRV22BT / EVV22BS23 kW heating22 kW cooling9,879 kWh/yr3$3,260
Actron Air CRV22BT / EAA22BS & EFV22BS23 kW heating22 kW cooling9,879 kWh/yr3$3,260
Panasonic U-224PZH3R8 / S-224PE4R25 kW heating22.4 kW cooling10,967 kWh/yr2.5$3,619
APAC S020OVR3SA / S020ILR1SA-18.9 kW heating22.4 kW cooling11,029 kWh/yr1.5$3,640
APAC S020OVR3SA / S020ILR1SA-TR18.9 kW heating22.4 kW cooling11,029 kWh/yr1.5$3,640

Heat pumps similar to the Mitsubishi Heavy Industries FDCA250VSA-W

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
APAC S024OVR3SA / S024ILR3SA-TR20.4 kW heating23.4 kW cooling11,785 kWh/yr1$3,889
APAC S024OVR3SA / S024IHR3SA-TR20.4 kW heating23.4 kW cooling11,785 kWh/yr1$3,889
Daikin RZYQ10TY1 / FDYQ250LCV126.8 kW heating24 kW cooling13,045 kWh/yr2$4,305
Toshiba RAV-GM2801AT8-A/RAV-RM2801DTP-E227 kW heating24 kW cooling12,847 kWh/yr1.5$4,240
Braemar SCHV24D3S/SDHV24D1S26 kW heating24 kW cooling13,685 kWh/yr1.5$4,516
Actron Air CRA230T / EAA230S & EFA230S23.5 kW heating22.6 kW cooling12,396 kWh/yr1.5$4,091
Actron Air CRA230T / EVA230S23.5 kW heating22.6 kW cooling12,396 kWh/yr1.5$4,091
Temperzone ISD 251LYX / OSA 251RLTFH23.3 kW heating22.5 kW cooling13,011 kWh/yr1$4,294

Compare FDCA250VSA-W/FDUA250VH with another model

Mitsubishi Heavy Industries FDCA250VSA-W specifications

Type
Reverse cycle
Configuration
Split system
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
23.50 kW
Cooling power input
7.70 kW
Rated heating capacity (7 Β°C)
28.00 kW
Heating power input
7.70 kW
EER, full load (tested)
3.16
COP, full load (tested)
3.68
Rated AEER
3.03
Rated ACOP
3.61
Standby power (PIA)
19.0 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Heavy Industries FDCA250VSA-W zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,2253,763
Coldresidential2.51.51,56611,699
Mixedcommercial––4,1721,857
Mixedresidential2.02.02,4614,215
Hotcommercial––9,448393
Hotresidential2.52.57,185613
Part-load test points (20 values)
h__h2_ext_cap_power_rated
7940 W
c__t1_half_cap_power_rated
2900 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
3100 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
21100 W
h__h1_half_cap_heat_cap_rated
14000 W
h__h2_is_capable_extended_load
Yes
c__low_temp_full_cap_power_rated
7037.8 W
c__low_temp_half_cap_power_rated
2480 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
11750 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_full_cap_cooling_cap_rated
25309.5 W
c__low_temp_half_cap_cooling_cap_rated
12500 W

New Zealand E3 registration details

Registration number
AAC7993
GEMS registration id
158677
Status
approved, available (self-reported)
Registration expires
6 January 2029
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.2:2012
MEPS
2019
Product class
Class 11

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: mhiaa.com.au. How the derived figures are calculated.